NFPA 13 · Worked example
Small office below the pressure floor
A K5.6 office head covers 110 ft² and has 6.5 psi residual. The flow can satisfy the Light Hazard density at this footprint.
Inputs
Remote sprinkler section
Edit inputsThe end head is below the applicable minimum pressure.
How to read this example
Read the pressure reserve alongside the flow reserve. A positive density-flow margin does not resolve a minimum-pressure shortfall.
Open the base calculatorCalculated values
- Delivered flow
- 14.28 GPM
- Required density flow
- 11 GPM
- Flow reserve
- 3.28 GPM
- Required head pressure
- 7 psi
- Minimum pressure floor
- 7 psi
- Reserve above pressure floor
- -0.5 psi
- Pressure for density alone
- 3.86 psi
- Design density
- 0.1 GPM/ft²
- Hydraulic coverage at entered density
- 142.77 ft²
Equations and assumptions
Q = K √PQ_required = density × areaP_required = max(7 psi, listed minimum, (Q_required/K)²)
The presets are common density/area design points for Light, Ordinary 1/2 and Extra 1/2. Pick the density for the adopted edition, occupancy and sprinkler listing.
The pressure is the residual at this sprinkler. Evaluate the remote design area, coverage limits, other operating sprinklers and water supply in the system calculation.