NFPA 13 · Worked example

Small office below the pressure floor

A K5.6 office head covers 110 ft² and has 6.5 psi residual. The flow can satisfy the Light Hazard density at this footprint.

Inputs

Sprinkler head
GPM/√psi

Enter the listed K-factor in the selected units.

psi
psi

The calculation uses at least 7 psi (about 0.48 bar).

Density and coverage
ft²

Remote sprinkler section

Worksheet units
Edit inputs
Remote sprinkler section · Input-linked engineering diagramDISCHARGE14.28GPMDENSITY FLOW11GPMMIN. PRESSURE7psiFLOW RESERVE3.28GPMBRANCH LINEK 5.6 GPM/√psiDensity 0.1 GPM/ft²110 ft² coverageDischarge vs. required flow+3.28 GPM0 GPM11 GPM target22 GPM
Below pressure floor

The end head is below the applicable minimum pressure.

How to read this example

Read the pressure reserve alongside the flow reserve. A positive density-flow margin does not resolve a minimum-pressure shortfall.

Open the base calculator

Calculated values

Delivered flow
14.28 GPM
Required density flow
11 GPM
Flow reserve
3.28 GPM
Required head pressure
7 psi
Minimum pressure floor
7 psi
Reserve above pressure floor
-0.5 psi
Pressure for density alone
3.86 psi
Design density
0.1 GPM/ft²
Hydraulic coverage at entered density
142.77 ft²

Equations and assumptions

  • Q = K √P
  • Q_required = density × area
  • P_required = max(7 psi, listed minimum, (Q_required/K)²)

The presets are common density/area design points for Light, Ordinary 1/2 and Extra 1/2. Pick the density for the adopted edition, occupancy and sprinkler listing.

The pressure is the residual at this sprinkler. Evaluate the remote design area, coverage limits, other operating sprinklers and water supply in the system calculation.