NFPA 13 · Worked example

Ordinary Group 2 vehicle bay

A vehicle service bay has 130 ft² per head and 12 psi residual at a K5.6 sprinkler. The selected density is 0.20 GPM/ft².

Inputs

Sprinkler head
GPM/√psi

Enter the listed K-factor in the selected units.

psi
psi

The calculation uses at least 7 psi (about 0.48 bar).

Density and coverage
ft²

Remote sprinkler section

Worksheet units
Edit inputs
Remote sprinkler section · Input-linked engineering diagramDISCHARGE19.4GPMDENSITY FLOW26GPMMIN. PRESSURE21.56psiFLOW RESERVE-6.6GPMBRANCH LINEK 5.6 GPM/√psiDensity 0.2 GPM/ft²130 ft² coverageDischarge vs. required flow-6.6 GPM0 GPM26 GPM target52 GPM
Density flow shortfall

The head pressure clears the floor, but discharge is below density times coverage.

How to read this example

The head meets the pressure floor, but density is the governing check. Compare both the flow deficit and the pressure needed to remove it.

Open the base calculator

Calculated values

Delivered flow
19.4 GPM
Required density flow
26 GPM
Flow reserve
-6.6 GPM
Required head pressure
21.56 psi
Minimum pressure floor
7 psi
Reserve above pressure floor
5 psi
Pressure for density alone
21.56 psi
Design density
0.2 GPM/ft²
Hydraulic coverage at entered density
96.99 ft²

Equations and assumptions

  • Q = K √P
  • Q_required = density × area
  • P_required = max(7 psi, listed minimum, (Q_required/K)²)

The presets are common density/area design points for Light, Ordinary 1/2 and Extra 1/2. Pick the density for the adopted edition, occupancy and sprinkler listing.

The pressure is the residual at this sprinkler. Evaluate the remote design area, coverage limits, other operating sprinklers and water supply in the system calculation.