NFPA 13 · Worked example
Ordinary Group 2 vehicle bay
A vehicle service bay has 130 ft² per head and 12 psi residual at a K5.6 sprinkler. The selected density is 0.20 GPM/ft².
Inputs
Remote sprinkler section
Edit inputsThe head pressure clears the floor, but discharge is below density times coverage.
How to read this example
The head meets the pressure floor, but density is the governing check. Compare both the flow deficit and the pressure needed to remove it.
Open the base calculatorCalculated values
- Delivered flow
- 19.4 GPM
- Required density flow
- 26 GPM
- Flow reserve
- -6.6 GPM
- Required head pressure
- 21.56 psi
- Minimum pressure floor
- 7 psi
- Reserve above pressure floor
- 5 psi
- Pressure for density alone
- 21.56 psi
- Design density
- 0.2 GPM/ft²
- Hydraulic coverage at entered density
- 96.99 ft²
Equations and assumptions
Q = K √PQ_required = density × areaP_required = max(7 psi, listed minimum, (Q_required/K)²)
The presets are common density/area design points for Light, Ordinary 1/2 and Extra 1/2. Pick the density for the adopted edition, occupancy and sprinkler listing.
The pressure is the residual at this sprinkler. Evaluate the remote design area, coverage limits, other operating sprinklers and water supply in the system calculation.