NFPA 13 · Worked example
Ordinary Group 1 workshop
A workshop bay uses 130 ft² per standard spray sprinkler. The hydraulically remote K5.6 head sees 15 psi.
Inputs
Remote sprinkler section
Edit inputsDischarge and end-head pressure both meet the entered targets.
How to read this example
Raise the coverage area to see how the required pressure changes with the square of required flow.
Open the base calculatorCalculated values
- Delivered flow
- 21.69 GPM
- Required density flow
- 19.5 GPM
- Flow reserve
- 2.19 GPM
- Required head pressure
- 12.13 psi
- Minimum pressure floor
- 7 psi
- Reserve above pressure floor
- 8 psi
- Pressure for density alone
- 12.13 psi
- Design density
- 0.15 GPM/ft²
- Hydraulic coverage at entered density
- 144.59 ft²
Equations and assumptions
Q = K √PQ_required = density × areaP_required = max(7 psi, listed minimum, (Q_required/K)²)
The presets are common density/area design points for Light, Ordinary 1/2 and Extra 1/2. Pick the density for the adopted edition, occupancy and sprinkler listing.
The pressure is the residual at this sprinkler. Evaluate the remote design area, coverage limits, other operating sprinklers and water supply in the system calculation.