NFPA 13 · Worked example

Ordinary Group 1 workshop

A workshop bay uses 130 ft² per standard spray sprinkler. The hydraulically remote K5.6 head sees 15 psi.

Inputs

Sprinkler head
GPM/√psi

Enter the listed K-factor in the selected units.

psi
psi

The calculation uses at least 7 psi (about 0.48 bar).

Density and coverage
ft²

Remote sprinkler section

Worksheet units
Edit inputs
Remote sprinkler section · Input-linked engineering diagramDISCHARGE21.69GPMDENSITY FLOW19.5GPMMIN. PRESSURE12.13psiFLOW RESERVE2.19GPMBRANCH LINEK 5.6 GPM/√psiDensity 0.15 GPM/ft²130 ft² coverageDischarge vs. required flow+2.19 GPM0 GPM19.5 GPM target39 GPM
Flow and pressure targets met

Discharge and end-head pressure both meet the entered targets.

How to read this example

Raise the coverage area to see how the required pressure changes with the square of required flow.

Open the base calculator

Calculated values

Delivered flow
21.69 GPM
Required density flow
19.5 GPM
Flow reserve
2.19 GPM
Required head pressure
12.13 psi
Minimum pressure floor
7 psi
Reserve above pressure floor
8 psi
Pressure for density alone
12.13 psi
Design density
0.15 GPM/ft²
Hydraulic coverage at entered density
144.59 ft²

Equations and assumptions

  • Q = K √P
  • Q_required = density × area
  • P_required = max(7 psi, listed minimum, (Q_required/K)²)

The presets are common density/area design points for Light, Ordinary 1/2 and Extra 1/2. Pick the density for the adopted edition, occupancy and sprinkler listing.

The pressure is the residual at this sprinkler. Evaluate the remote design area, coverage limits, other operating sprinklers and water supply in the system calculation.