NFPA 14 · Worked example

Base outlet exactly at 175 psi

The maximum static at a six-floor riser base is 175 psi. Its required base residual remains below that value.

Inputs

Demand basis
Riser geometry and pressure

One representative outlet per floor.

ft
psi
psi

Class I riser elevation

Worksheet units
Edit inputs
Class I riser elevation · Input-linked engineering diagramCLASS I FLOW750GPMSTATIC RISE28.15psiBASE RESIDUAL139.15psiPRV FLOORS0FLOOR 6FLOOR 1TOP OUTLET100 psi flowingPRV REVIEWNo floors flaggedBASE MAXIMUM175 psiHighest outlet vs. 175 psi screen0 psi0 psi175 psi target350 psi
Outlet pressure screen clear

The modeled floor outlets stay at or below the entered scope’s 175 psi screen.

How to read this example

The threshold is exceeded only above 175 psi. Check the effect of any additional static pressure from the selected supply.

Open the base calculator

Calculated values

Class I demand after cap
750 GPM
Flow before cap
750 GPM
Applied flow cap
1,000 GPM
Elevation head to top outlet
28.15 psi
Required base residual
139.15 psi
Estimated top static
146.86 psi
Governing base outlet pressure
175 psi
Reserve below outlet pressure ceiling
0 psi
Floors flagged for pressure review
0
First floor within pressure screen
1
Outlet pressure by floor 6 rows
Outlet pressure by floor
FloorRiseftStaticpsiFlowingpsiPRV review
10175139.1Clear
213169.4131.3Clear
326163.7123.5Clear
439158.1115.7Clear
552152.5107.8Clear
665146.9100Clear

Equations and assumptions

  • Q = min(500 + 250 (n − 1), 1000 or 1250 GPM)
  • P_base,flowing = 100 psi + 0.433 Δz + friction
  • P_static at floor = P_base,static − 0.433 × floor rise

This is the common vertical Class I demand basis. The remote 2½-inch outlet target is 100 psi residual. Special layouts, large floor areas and combined-system criteria can change the flow basis.

The floor schedule assumes evenly spaced outlets and prorates the entered flowing loss by elevation. A floor is flagged if static or modeled residual exceeds 175 psi. Verify listed pressure regulation using the available inlet static and residual, valve ratings and the adopted edition.

Residual and static inputs describe separate conditions. Reconcile a static pressure below the required flowing base or any modeled negative static before selecting a zone.