NFPA 14

Class I standpipe demand and PRV zoning

Estimate standpipe inlet demand and locate floors whose 2½-inch outlets exceed the 175 psi pressure screen.

Inputs

Demand basis
Riser geometry and pressure

One representative outlet per floor.

ft
psi
psi

Class I riser elevation

Worksheet units
Edit inputs
Class I riser elevation · Input-linked engineering diagramCLASS I FLOW1,000GPMSTATIC RISE81.4psiBASE RESIDUAL197.4psiPRV FLOORS8FLOOR 16FLOOR 1TOP OUTLET100 psi flowingPRV REVIEWF1–F8BASE MAXIMUM215 psiHighest outlet vs. 175 psi screen-40 psi0 psi175 psi target350 psi
Review the pressure zone

The outlet schedule flags static or modeled residual pressure above 175 psi.

Calculated values

Class I demand after cap
1,000 GPM
Flow before cap
1,000 GPM
Applied flow cap
1,000 GPM
Elevation head to top outlet
81.4 psi
Required base residual
197.4 psi
Estimated top static
133.6 psi
Governing base outlet pressure
215 psi
Reserve below outlet pressure ceiling
-40 psi
Floors flagged for pressure review
8
First floor within pressure screen
9
Outlet pressure by floor 16 rows
Outlet pressure by floor
FloorRiseftStaticpsiFlowingpsiPRV review
10215197.4Both
212.5209.6190.9Both
325.1204.1184.4Both
437.6198.7177.9Both
550.1193.3171.4Static
662.7187.9164.9Static
775.2182.4158.4Static
887.7177151.9Static
9100.3171.6145.5Clear
10112.8166.2139Clear
11125.3160.7132.5Clear
12137.9155.3126Clear
13150.4149.9119.5Clear
14162.9144.4113Clear
15175.5139106.5Clear
16188133.6100Clear

Equations and assumptions

  • Q = min(500 + 250 (n − 1), 1000 or 1250 GPM)
  • P_base,flowing = 100 psi + 0.433 Δz + friction
  • P_static at floor = P_base,static − 0.433 × floor rise

This is the common vertical Class I demand basis. The remote 2½-inch outlet target is 100 psi residual. Special layouts, large floor areas and combined-system criteria can change the flow basis.

The floor schedule assumes evenly spaced outlets and prorates the entered flowing loss by elevation. A floor is flagged if static or modeled residual exceeds 175 psi. Verify listed pressure regulation using the available inlet static and residual, valve ratings and the adopted edition.

Residual and static inputs describe separate conditions. Reconcile a static pressure below the required flowing base or any modeled negative static before selecting a zone.

Source references

Worked examples