NFPA 14 · Worked example

Partly sprinklered building flow cap

Six risers are modeled for a building that is not fully sprinklered. The remote outlet is 112 ft above the base.

Inputs

Demand basis
Riser geometry and pressure

One representative outlet per floor.

m
bar
bar

Class I riser elevation

Worksheet units
Edit inputs
Class I riser elevation · Input-linked engineering diagramCLASS I FLOW4,731.76L/minSTATIC RISE3.34barBASE RESIDUAL11.41barPRV FLOORS1FLOOR 10FLOOR 1TOP OUTLET6.89 bar flowingPRV REVIEWF1BASE MAXIMUM12.41 barHighest outlet vs. 175 psi screen-0.34 bar0 bar12.07 bar target24.13 bar
Review the pressure zone

The outlet schedule flags static or modeled residual pressure above 175 psi.

How to read this example

The selected flow cap is 1,250 GPM. The floor pressure schedule separately identifies outlets to review.

Open the base calculator

Calculated values

Class I demand after cap
4,731.76 L/min
Flow before cap
6,624.47 L/min
Applied flow cap
4,731.76 L/min
Elevation head to top outlet
3.34 bar
Required base residual
11.41 bar
Estimated top static
9.07 bar
Governing base outlet pressure
12.41 bar
Reserve below outlet pressure ceiling
-0.34 bar
Floors flagged for pressure review
1
First floor within pressure screen
2
Outlet pressure by floor 10 rows
Outlet pressure by floor
FloorRisemStaticbarFlowingbarPRV review
1012.411.4Static
23.81210.9Clear
37.611.710.4Clear
411.411.39.9Clear
515.210.99.4Clear
61910.68.9Clear
722.810.28.4Clear
826.69.87.9Clear
930.39.47.4Clear
1034.19.16.9Clear

Equations and assumptions

  • Q = min(500 + 250 (n − 1), 1000 or 1250 GPM)
  • P_base,flowing = 100 psi + 0.433 Δz + friction
  • P_static at floor = P_base,static − 0.433 × floor rise

This is the common vertical Class I demand basis. The remote 2½-inch outlet target is 100 psi residual. Special layouts, large floor areas and combined-system criteria can change the flow basis.

The floor schedule assumes evenly spaced outlets and prorates the entered flowing loss by elevation. A floor is flagged if static or modeled residual exceeds 175 psi. Verify listed pressure regulation using the available inlet static and residual, valve ratings and the adopted edition.

Residual and static inputs describe separate conditions. Reconcile a static pressure below the required flowing base or any modeled negative static before selecting a zone.