NFPA 14 · Worked example

Fully sprinklered multiriser flow cap

Five Class I risers serve a sprinklered building with a representative 12-floor vertical run.

Inputs

Demand basis
Riser geometry and pressure

One representative outlet per floor.

ft
psi
psi

Class I riser elevation

Worksheet units
Edit inputs
Class I riser elevation · Input-linked engineering diagramCLASS I FLOW1,000GPMSTATIC RISE56.29psiBASE RESIDUAL170.29psiPRV FLOORS2FLOOR 12FLOOR 1TOP OUTLET100 psi flowingPRV REVIEWF1–F2BASE MAXIMUM184 psiHighest outlet vs. 175 psi screen-9 psi0 psi175 psi target350 psi
Review the pressure zone

The outlet schedule flags static or modeled residual pressure above 175 psi.

How to read this example

Compare uncapped 1,500 GPM with the 1,000 GPM screening cap. Confirm the applicable project flow basis.

Open the base calculator

Calculated values

Class I demand after cap
1,000 GPM
Flow before cap
1,500 GPM
Applied flow cap
1,000 GPM
Elevation head to top outlet
56.29 psi
Required base residual
170.29 psi
Estimated top static
127.71 psi
Governing base outlet pressure
184 psi
Reserve below outlet pressure ceiling
-9 psi
Floors flagged for pressure review
2
First floor within pressure screen
3
Outlet pressure by floor 12 rows
Outlet pressure by floor
FloorRiseftStaticpsiFlowingpsiPRV review
10184170.3Static
211.8178.9163.9Static
323.6173.8157.5Clear
435.5168.6151.1Clear
547.3163.5144.7Clear
659.1158.4138.3Clear
770.9153.3132Clear
882.7148.2125.6Clear
994.5143.1119.2Clear
10106.4137.9112.8Clear
11118.2132.8106.4Clear
12130127.7100Clear

Equations and assumptions

  • Q = min(500 + 250 (n − 1), 1000 or 1250 GPM)
  • P_base,flowing = 100 psi + 0.433 Δz + friction
  • P_static at floor = P_base,static − 0.433 × floor rise

This is the common vertical Class I demand basis. The remote 2½-inch outlet target is 100 psi residual. Special layouts, large floor areas and combined-system criteria can change the flow basis.

The floor schedule assumes evenly spaced outlets and prorates the entered flowing loss by elevation. A floor is flagged if static or modeled residual exceeds 175 psi. Verify listed pressure regulation using the available inlet static and residual, valve ratings and the adopted edition.

Residual and static inputs describe separate conditions. Reconcile a static pressure below the required flowing base or any modeled negative static before selecting a zone.