NFPA 14 · Worked example
Base outlet exactly at 175 psi
The maximum static at a six-floor riser base is 175 psi. Its required base residual remains below that value.
Inputs
Class I riser elevation
Edit inputsThe modeled floor outlets stay at or below the entered scope’s 175 psi screen.
How to read this example
The threshold is exceeded only above 175 psi. Check the effect of any additional static pressure from the selected supply.
Open the base calculatorCalculated values
- Class I demand after cap
- 750 GPM
- Flow before cap
- 750 GPM
- Applied flow cap
- 1,000 GPM
- Elevation head to top outlet
- 28.15 psi
- Required base residual
- 139.15 psi
- Estimated top static
- 146.86 psi
- Governing base outlet pressure
- 175 psi
- Reserve below outlet pressure ceiling
- 0 psi
- Floors flagged for pressure review
- 0
- First floor within pressure screen
- 1
Outlet pressure by floor 6 rows
| Floor | Riseft | Staticpsi | Flowingpsi | PRV review |
|---|---|---|---|---|
| 1 | 0 | 175 | 139.1 | Clear |
| 2 | 13 | 169.4 | 131.3 | Clear |
| 3 | 26 | 163.7 | 123.5 | Clear |
| 4 | 39 | 158.1 | 115.7 | Clear |
| 5 | 52 | 152.5 | 107.8 | Clear |
| 6 | 65 | 146.9 | 100 | Clear |
Equations and assumptions
Q = min(500 + 250 (n − 1), 1000 or 1250 GPM)P_base,flowing = 100 psi + 0.433 Δz + frictionP_static at floor = P_base,static − 0.433 × floor rise
This is the common vertical Class I demand basis. The remote 2½-inch outlet target is 100 psi residual. Special layouts, large floor areas and combined-system criteria can change the flow basis.
The floor schedule assumes evenly spaced outlets and prorates the entered flowing loss by elevation. A floor is flagged if static or modeled residual exceeds 175 psi. Verify listed pressure regulation using the available inlet static and residual, valve ratings and the adopted edition.
Residual and static inputs describe separate conditions. Reconcile a static pressure below the required flowing base or any modeled negative static before selecting a zone.