Intermittent fuel gas supply

An intermittent fuel-gas branch uses the C = 125 comparison for a 106 mm line.

What to check

The screen tracks velocity in the gas at operating pressure. Confirm whether the intermittent service basis applies.

Operating readout

Edit inputs ↓
Outlet press.
762.45kPa(a)
Pressure drop
37.55kPa
Outlet velocity
16.98m/s
Erosion use
28.13%
Within velocity screening limitThe outlet is within the selected API RP 14E comparison value.
Gas line section and longitudinal pressure profileISOTHERMAL GAS LINEkPa(a)P₁ 800P₂ 762Δz 0 mLONGITUDINAL PRESSUREkPa(a)80076200.25 kmOUTLET EROSION USE28.1%
The line follows the entered elevation change. The plot uses the pressure-squared model at each distance along the run.
Calculated details
Inlet gas velocity
16.18m/s
Inlet RP 14E comparison
58.91m/s
Outlet RP 14E comparison
60.35m/s
Inlet gas density
6.7kg/m³
Outlet gas density
6.38kg/m³
Elevation correction exponent
0
Outlet isothermal Mach
0.0491
Mass flow used
3,443.91kg/h

Operating inputs

Pipeline duty
kPa(a)
Nm³/h
km
mm
m
Positive for an uphill run.
Gas and resistance
°C
%

Calculation basis

Solve the pressure-squared balance

With constant Z and temperature, use s = 2gΔz/(ZRₛT) and equivalent length L·expm1(s)/s. Solve for P₂ in the pressure-squared difference P₁² − eˢP₂². The Darcy mode uses the entered friction factor. Weymouth and Panhandle B use their published US-unit flow coefficients.

Compare velocity

Convert standard volumetric flow to mass, then divide by local density and flow area. The RP 14E comparison is C/√ρ in ft/s with density in lb/ft³. The outlet governs for a declining, isothermal pressure profile.