GasCompressLab

API 521 · Annexes C and F

API 521 flare radiation & stack height

Estimate subsonic flare tip Mach, wind-shifted flame radiation, receptor stack height and ground screening zones.

Operating readout

Edit inputs ↓
Receptor flux
1.99kW/m²
Tip Mach
0.285
Min. height
0m
Flame length
41.76m
Within receptor screening levelsModeled receptor radiation and tip Mach meet the selected limits.
Flare stack elevation and ground radiation zonesFLARE STACK ELEVATIONmWind 8 m/sGROUND PLANkW/m²1.5866.6 m4.730 m9.460 mRECEPTOR LIMIT USED42.1%
Ground zones share the flame center’s ground projection. The point-source center and receptor move with the entered wind and geometry.
Calculated details
Tip gas velocity
104.5m/s
Total heat release
430,833.33kW
Peak ground flux
3.29kW/m²
Flame center downwind shift
14.62m
Flame center above grade
50.01m
Distance from flame center to receptor
64.28m
Service Mach target
0.5
Minimum tip ID for selected Mach
290.65mm
Wind-to-jet velocity ratio
0.077
Downwind extent · 1.58 kW/m²
66.65m
Downwind extent · 4.73 kW/m²
0m
Downwind extent · 9.46 kW/m²
0m

Operating inputs

Flare duty
kg/h
kg/kmol
MJ/kg
%
0.15–0.30 is an illustrative range. Use tip-specific data.
mm
m
m/s
m
kW/m²
Screening landmarks include 1.58, 4.73 and 9.46 kW/m².
Tip and atmosphere
kPa(a)
°C

Calculation basis

Tip and flame

Use actual flow at the flare tip divided by tip area. The API 521 isothermal Mach screen uses √(ZRₛT). Estimate length using a power-law fit to the Annex C/F reference curve and wind offsets by interpolation of flame distortion.

Radiation and height

Use q = τFQ/(4πD²), with D measured from the wind-shifted flame center. Solve for the minimum stack height at the entered receptor. Ground contours are circles centered on the flame projection. Extents are measured downwind from the stack.

Worked examples