Weymouth · Panhandle B · RP 14E
Panhandle B regional transmission
A long transmission segment uses Panhandle B at 182,000 Nm³/h and a 610 mm ID.
Try Weymouth to see model sensitivity while keeping the same base, geometry and gas properties.
Operating readout
Edit inputs ↓- Outlet press.
- 7,353.67kPa(a)
- Pressure drop
- 246.33kPa
- Outlet velocity
- 2.28m/s
- Erosion use
- 14.34%
Calculated details
- Inlet gas velocity
- 2.21m/s
- Inlet RP 14E comparison
- 15.65m/s
- Outlet RP 14E comparison
- 15.91m/s
- Inlet gas density
- 60.75kg/m³
- Outlet gas density
- 58.78kg/m³
- Elevation correction exponent
- 0.00941
- Outlet isothermal Mach
- 0.0065
- Mass flow used
- 141,116.37kg/h
Operating inputs
Operating inputs
- Flow equation
- Panhandle B
- Inlet pressure P₁
- 7,600kPa(a)
- Standard gas flow
- 182,000Nm³/h
- Run length
- 92km
- Pipe inside diameter
- 610mm
- Outlet elevation change
- 60m
- Average gas temperature
- 24°C
- Average compressibility Z
- 0.88
- Gas gravity (air = 1)
- 0.6
- Pipe efficiency E
- 92%
- API RP 14E service
- Continuous · C = 100
Calculated details
- Inlet gas velocity
- 2.21m/s
- Inlet RP 14E comparison
- 15.65m/s
- Outlet RP 14E comparison
- 15.91m/s
- Inlet gas density
- 60.75kg/m³
- Outlet gas density
- 58.78kg/m³
- Elevation correction exponent
- 0.00941
- Outlet isothermal Mach
- 0.0065
- Mass flow used
- 141,116.37kg/h
Steady single-phase dry gas. Treat Weymouth and Panhandle B as empirical alternatives within their applicable flow ranges. The model requires a declining pressure profile and flags a depleted pressure-squared budget. API RP 14E is an offshore production piping practice, so the displayed velocity comparison is only a screen for this dry-gas case. Confirm erosion, corrosion, solids and transient behavior separately.
Calculation basis
Solve the pressure-squared balance
With constant Z and temperature, use s = 2gΔz/(ZRₛT) and equivalent length L·expm1(s)/s. Solve for P₂ in the pressure-squared difference P₁² − eˢP₂². The Darcy mode uses the entered friction factor. Weymouth and Panhandle B use their published US-unit flow coefficients.
Compare velocity
Convert standard volumetric flow to mass, then divide by local density and flow area. The RP 14E comparison is C/√ρ in ft/s with density in lb/ft³. The outlet governs for a declining, isothermal pressure profile.
Related worked examples
-
Weymouth trunkline transfer →
A 356 mm ID trunkline carries 54,000 Nm³/h of sweet gas through a mild uphill run.
-
Darcy short plant transfer line →
A short dry-gas run is screened with an entered Darcy friction factor of 0.018.
-
Downhill export segment →
A descending fuel gas line has enough friction loss to retain a lower outlet pressure.
-
Intermittent fuel gas supply →
An intermittent fuel-gas branch uses the C = 125 comparison for a 106 mm line.
-
High-velocity plant header →
A short section with a high volumetric loading illustrates when RP 14E comparison can be exceeded.