Pitched atrium with ground snow input

An atrium uses a supplied ground-to-roof conversion and a horizontal projection.

GANA setting-block screen

Inputs

Slope, glass and loading
°
m
m
mm
kg/m³
kPa
kPa

Positive presses toward the frame.

Setting blocks
mm
Shore A
%

25% places blocks at the quarter points.

MPa

Use the block manufacturer’s allowable pressure.

Screening result

Block length, fit or bearing is outside the entered limit.

Fail
Normal load
2.13kPa
In-plane force
4560N
Min. block
113.6mm
Block bearing
0.93MPa
Sloped-glass free-body diagram and setting blocksSkylight snow and blocks. Normal load 2.13 kPa. In-plane force 4560 N. Min. block 113.6 mm. Block bearing 0.93 MPa.Sloped glass load components34 ° from horizontalWeightNormalThrustLower edge block placementBlock length 140 mm25 % from each cornerGoverning block demand0%100% limit200%+

Calculation details

Total glass weight
1784.101 N
Total glass mass
181.928 kg
Dead load per glass area
0.43 kPa
Snow resultant per glass area
1.534 kPa
Glass-only downslope thrust
997.657 N
Gravity and snow thrust per block
2279.986 N
Minimum block width (glass + 1/8 in)
20.695 mm
Clearance from corner to block end
370 mm

Formula trace in SI

  1. Weight and snow basis

    W = ρ t A g; p_snow = p_roof cos θ for plan-area pressure

    W = 1784.101 N, converted p_snow = 1.534 kPa.

  2. Slope components

    qn = (pd + ps) cos θ + pw; F∥ = (pd + ps) A sin θ

    Angle 34 °, qn = 2.128 kPa, F∥ = 4559.971 N.

  3. Block length

    ℓmin = max(4 in, 0.1 in × area in ft²)

    Per-block minimum 113.561 mm, provided 140 mm.

  4. Edge bearing

    pblock = F∥ / (2 ℓblock tglass)

    0.93 MPa versus 0.85 MPa allowance.