GroundGridLab · IEEE 80-2013 · Onderdonk
Annealed copper grid conductor
A buried copper link with an exothermic connection is screened for a 12 kA equivalent RMS fault for half a second.
Candidate meets thermal area. The comparison uses the selected limit for Annealed Cu · exothermic.
- Minimum cross-section
- 30.195 mm²
- Next standard size
- 35 mm²
- Candidate utilization
- 43.136 %
- Joint / material limit
- 1,083 °C
Inputs
| Material / connection | Annealed Cu · exothermic |
|---|---|
| Starting conductor temperature | 40 °C |
| Candidate cross-section | 70 mm² |
| Equivalent RMS conductor current | 12 kA |
| Fault clearing time | 0.5 s |
Derived values
| Minimum in both systems | 30.195 mm² / 59.591 kcmil |
|---|---|
| Next metric size | 35 mm² |
| Next AWG / kcmil size | 2 AWG |
| Candidate time at entered current | 2.6871 s |
| Candidate current at entered time | 27.819 kA |
| Thermal I²t utilization | 18.607 % |
| Reference resistivity | 1.72 μΩ·cm |
| Volumetric heat capacity | 3.4 J/(cm³·°C) |
Verify the tested connection limit, actual equivalent RMS current, fault duty, corrosion allowance and mechanical minimum. Use these checks together to specify the conductor.