GroundGridLab · IEEE 80-2013 · Onderdonk
Brazed copper transition
A 450 °C connection cap is used to screen a brazed transition between the bus equipment and a ground lead.
Candidate meets thermal area. The comparison uses the selected limit for Hard-drawn Cu · brazed.
- Minimum cross-section
- 83.495 mm²
- Next standard size
- 95 mm²
- Candidate utilization
- 69.58 %
- Joint / material limit
- 450 °C
Inputs
| Material / connection | Hard-drawn Cu · brazed |
|---|---|
| Starting conductor temperature | 35 °C |
| Candidate cross-section | 120 mm² |
| Equivalent RMS conductor current | 20 kA |
| Fault clearing time | 0.8 s |
Derived values
| Minimum in both systems | 83.495 mm² / 164.78 kcmil |
|---|---|
| Next metric size | 95 mm² |
| Next AWG / kcmil size | 3/0 AWG |
| Candidate time at entered current | 1.6524 s |
| Candidate current at entered time | 28.744 kA |
| Thermal I²t utilization | 48.413 % |
| Reference resistivity | 1.78 μΩ·cm |
| Volumetric heat capacity | 3.4 J/(cm³·°C) |
Verify the tested connection limit, actual equivalent RMS current, fault duty, corrosion allowance and mechanical minimum. Use these checks together to specify the conductor.