GroundGridLab · IEEE 80-2013 · Onderdonk
Bolted copper connection
A removable copper ground strap uses a 250 °C screening cap at the joint and starts at a warm ambient temperature.
Candidate meets thermal area. The comparison uses the selected limit for Hard-drawn Cu · bolted.
- Minimum cross-section
- 84.152 mm²
- Next standard size
- 95 mm²
- Candidate utilization
- 88.581 %
- Joint / material limit
- 250 °C
Inputs
| Material / connection | Hard-drawn Cu · bolted |
|---|---|
| Starting conductor temperature | 55 °C |
| Candidate cross-section | 95 mm² |
| Equivalent RMS conductor current | 16 kA |
| Fault clearing time | 0.7 s |
Derived values
| Minimum in both systems | 84.152 mm² / 166.08 kcmil |
|---|---|
| Next metric size | 95 mm² |
| Next AWG / kcmil size | 3/0 AWG |
| Candidate time at entered current | 0.8921 s |
| Candidate current at entered time | 18.063 kA |
| Thermal I²t utilization | 78.466 % |
| Reference resistivity | 1.78 μΩ·cm |
| Volumetric heat capacity | 3.4 J/(cm³·°C) |
Verify the tested connection limit, actual equivalent RMS current, fault duty, corrosion allowance and mechanical minimum. Use these checks together to specify the conductor.