Worked example · IEEE 80-2013 · Onderdonk

Bolted copper connection

Adiabatic fault-current sizing of ground conductors using material constants and joint temperature limits.

A removable copper ground strap uses a 250 °C screening cap at the joint and starts at a warm ambient temperature.

Candidate meets thermal area

The comparison uses the selected limit for Hard-drawn Cu · bolted.

Minimum cross-section
84.152 mm²
Next standard size
95 mm²
Candidate utilization
88.581 %
Joint / material limit
250 °C

Inputs

Conductor and joint
°C
mm²
Fault duty
kA
s

Time–current thermal curves

Live schematic
Min. area84.15 mm²Next size95 mm²Utilization88.58 %Temp limit250 °CFUSING TIME / s0.03770.82217.95.331648RMS fault current / kACONDUCTOR CROSS-SECTIONSCandidateMinimum thermal area95 mm²84.15 mm²70 mm²120 mm²Required / candidate area88.58%
Logarithmic axes. The candidate curve and two standard-size references use equal material, joint and initial temperature.

Derived values & comparisons
Minimum in both systems84.152 mm² / 166.08 kcmil
Next metric size95 mm²
Next AWG / kcmil size3/0 AWG
Candidate time at entered current0.8921 s
Candidate current at entered time18.063 kA
Thermal I²t utilization78.466 %
Reference resistivity1.78 μΩ·cm
Volumetric heat capacity3.4 J/(cm³·°C)

Screening scope. Verify the tested connection limit, actual equivalent RMS current, fault duty, corrosion allowance and mechanical minimum. Use these checks together to specify the conductor.

Try this. Switch to the brazed preset to isolate the effect of the temperature ceiling on required area.

Calculation method

IEEE Std 80-2013 §11.3.1, equations 45–46 and Tables 1–2. IEEE Eq. 45 gives mm² from kA, seconds, TCAP in J/(cm³·°C), ρᵣ in μΩ·cm, and Celsius temperatures. The result is converted to kcmil using 1 kcmil = 0.506707479 mm².

The log term is ln[(K₀ + Tₘ)/(K₀ + Tₐ)]. The candidate utilization is required area / entered area. The thermal-energy utilization is its square. Standard sizes round up from the unrounded area.

The brazed and bolted connection caps are screening settings. Aluminum EC-0 and 5005-H19 resistivity and temperature coefficients come from NBS Handbook 109, Table 1. The aluminum heat capacity and lower melting limits are engineering approximations. Zinc-coated rod constants serve as a galvanized-steel proxy.

Standards and model assumptions