GroundGridLab · Dwight · uniform soil
Square array with interior electrodes
A facility electrode grid has perimeter and interior rods in clay. The available footprint limits minimum center spacing.
Resistance above target. The first count meeting the target in this layout is 30.
- Array resistance
- 4.3895 Ω
- Single-rod resistance
- 25.12 Ω
- Array utilization
- 35.767 %
- Rods to reach target
- 30 rods
Inputs
| Native soil resistivity | 75 Ω·m |
|---|---|
| Driven rod length | 3 m |
| Rod radius | 8 mm |
| Backfill sleeve thickness | 0 mm |
| Rod layout | Square with interior rods |
| Number of rods | 16 rods |
| Minimum rod centers | 1.8 m |
| Array resistance target | 3 Ω |
Derived values
| Bare single rod | 25.12 Ω |
|---|---|
| Ideal uncoupled array | 1.57 Ω |
| Coupling factor vs. ideal | 2.7959 × |
| Center spacing / driven length | 0.6 × |
| Effective sleeve diameter | 16 mm |
| Maximum modeled count | 128 rods |
The sleeve is an ideal full-length cylinder. Uniform soil, perfect bonding and equal rod currents are assumed. Use field resistance tests and a layered model for design.