GroundGridLab · Dwight · uniform soil
Hollow square tower footing
A tower footing has eight electrodes around the outside of a small fenced pad. The hollow square avoids interior foundation conflicts.
Resistance above target. The first count meeting the target in this layout is 14.
- Array resistance
- 11.271 Ω
- Single-rod resistance
- 56.541 Ω
- Array utilization
- 62.708 %
- Rods to reach target
- 14 rods
Inputs
| Native soil resistivity | 140 Ω·m |
|---|---|
| Driven rod length | 2.4 m |
| Rod radius | 8 mm |
| Backfill sleeve thickness | 0 mm |
| Rod layout | Hollow square |
| Number of rods | 8 rods |
| Minimum rod centers | 2.7 m |
| Array resistance target | 7 Ω |
Derived values
| Bare single rod | 56.541 Ω |
|---|---|
| Ideal uncoupled array | 7.0676 Ω |
| Coupling factor vs. ideal | 1.5947 × |
| Center spacing / driven length | 1.125 × |
| Effective sleeve diameter | 16 mm |
| Maximum modeled count | 128 rods |
The sleeve is an ideal full-length cylinder. Uniform soil, perfect bonding and equal rod currents are assumed. Use field resistance tests and a layered model for design.