GroundGridLab · Dwight · uniform soil
Rocky site resistance target
A shallow rocky site has poor soil conductivity and an aggressive comparison target. The array study tests whether adding rods alone meets the target.
Resistance above target. No layout in the modeled count range meets the entered target.
- Array resistance
- 55.951 Ω
- Single-rod resistance
- 423.11 Ω
- Array utilization
- 63.018 %
- Rods to reach target
- —
Inputs
| Native soil resistivity | 900 Ω·m |
|---|---|
| Driven rod length | 2 m |
| Rod radius | 8 mm |
| Backfill sleeve thickness | 0 mm |
| Rod layout | Hollow square |
| Number of rods | 12 rods |
| Minimum rod centers | 3 m |
| Array resistance target | 0.5 Ω |
Derived values
| Bare single rod | 423.11 Ω |
|---|---|
| Ideal uncoupled array | 35.259 Ω |
| Coupling factor vs. ideal | 1.5869 × |
| Center spacing / driven length | 1.5 × |
| Effective sleeve diameter | 16 mm |
| Maximum modeled count | 128 rods |
The sleeve is an ideal full-length cylinder. Uniform soil, perfect bonding and equal rod currents are assumed. Use field resistance tests and a layered model for design.