Worked example · IEC 62305-3 · NFPA 780

LPL I rooftop equipment

Single-mast reach, equal-mast midpoint sag and a simplified separation-distance check.

A rooftop structure is used as a flat datum for two equal air terminals. The smaller 20 m sphere screens a duct at midspan.

Clearance checks met

Compare centerline clearance and the available separation against the simplified model.

Sphere radius
20 m
Single-mast reach
2.2238 m
Midspan clearance
0.030303 m
Required separation
0.32 m

Inputs

Sphere and masts
m
m
m
IEC separation distance
×
×
m
m

Equal-mast rolling-sphere section

Live schematic
Sphere R20 mMast reach2.224 mClearance0.0303 mSeparation0.32 mROLLING SPHERE · SECTIONMast span 16 mMIDSPAN CLEARANCEMast tip height5 mSphere sag at center1.67 mEquipment height3.3 mClearance at center0.0303 mMast span / sphere diameter40%Required / available separation64%
Equal mast tips and one centerline section. Height and width share a scale in the envelope drawing.

Derived values & comparisons
Midspan sag1.6697 m
Midspan envelope height3.3303 m
Single mast effective height5 m
Span must be below40 m
Separation margin0.18 m
Lightning protection factor kᵢ0.08 ×

Screening scope. Evaluate the whole site in 3D, including roof edges, sides, other strike points and current paths. The separation-distance screen uses simplified IEC factors.

Try this. Reduce spacing while leaving the roof equipment height fixed to recover midspan clearance.

Calculation method

IEC 62305-3:2024 and NFPA 780 rolling-sphere geometry. IEC LPL I–IV use 20, 30, 45 and 60 m. The NFPA radius preset is 150 ft (45.72 m). The NFPA geometry option keeps the IEC separation estimate separate and requires a user-supplied kᵢ.

The single-mast reach at object height hₓ equals √[h(2R − h)] − √[hₓ(2R − hₓ)] with h capped at R. Above the capped height there is no positive single-mast radius in this screen.

For equal masts spaced d apart, midpoint penetration is R − √(R² − d²/4), with d < 2R. Midpoint clearance must be positive. Contact with the rolling sphere leaves the object exposed. The separation estimate is kᵢk꜀l/kₘ.

Standards and model assumptions