Equal masts beside a transformer
Two 14 m masts flank a 7 m transformer clearance envelope. IEC LPL II establishes the 30 m sphere radius.
Clearance checks met. Compare centerline clearance and the available separation against the simplified model.
- Sphere radius
- 30 m
- Single-mast reach
- 6.1158 m
- Midspan clearance
- 4.4955 m
- Required separation
- 0.54 m
Inputs
| Lightning protection level | IEC LPL II |
|---|---|
| Equal mast height | 14 m |
| Object height above datum | 7 m |
| Mast center spacing | 24 m |
| Current sharing k꜀ | 0.5 × |
| Insulating material kₘ | 1 × |
| Length to bonding point | 18 m |
| Available separation | 0.8 m |
Derived values
| Midspan sag | 2.5045 m |
|---|---|
| Midspan envelope height | 11.495 m |
| Single mast effective height | 14 m |
| Span must be below | 60 m |
| Separation margin | 0.26 m |
| Lightning protection factor kᵢ | 0.06 × |
Evaluate the whole site in 3D, including roof edges, sides, other strike points and current paths. The separation-distance screen uses simplified IEC factors.