Worked example · IEC 62305-3 · NFPA 780

Equal masts beside a transformer

Single-mast reach, equal-mast midpoint sag and a simplified separation-distance check.

Two 14 m masts flank a 7 m transformer clearance envelope. IEC LPL II establishes the 30 m sphere radius.

Clearance checks met

Compare centerline clearance and the available separation against the simplified model.

Sphere radius
30 m
Single-mast reach
6.1158 m
Midspan clearance
4.4955 m
Required separation
0.54 m

Inputs

Sphere and masts
m
m
m
IEC separation distance
×
×
m
m

Equal-mast rolling-sphere section

Live schematic
Sphere R30 mMast reach6.116 mClearance4.495 mSeparation0.54 mROLLING SPHERE · SECTIONMast span 24 mMIDSPAN CLEARANCEMast tip height14 mSphere sag at center2.505 mEquipment height7 mClearance at center4.495 mMast span / sphere diameter40%Required / available separation67.5%
Equal mast tips and one centerline section. Height and width share a scale in the envelope drawing.

Derived values & comparisons
Midspan sag2.5045 m
Midspan envelope height11.495 m
Single mast effective height14 m
Span must be below60 m
Separation margin0.26 m
Lightning protection factor kᵢ0.06 ×

Screening scope. Evaluate the whole site in 3D, including roof edges, sides, other strike points and current paths. The separation-distance screen uses simplified IEC factors.

Try this. Increase mast separation and track how the protected height at midspan changes.

Calculation method

IEC 62305-3:2024 and NFPA 780 rolling-sphere geometry. IEC LPL I–IV use 20, 30, 45 and 60 m. The NFPA radius preset is 150 ft (45.72 m). The NFPA geometry option keeps the IEC separation estimate separate and requires a user-supplied kᵢ.

The single-mast reach at object height hₓ equals √[h(2R − h)] − √[hₓ(2R − hₓ)] with h capped at R. Above the capped height there is no positive single-mast radius in this screen.

For equal masts spaced d apart, midpoint penetration is R − √(R² − d²/4), with d < 2R. Midpoint clearance must be positive. Contact with the rolling sphere leaves the object exposed. The separation estimate is kᵢk꜀l/kₘ.

Standards and model assumptions