IEC 60364 · NEC 250 context

Earth-Fault Loop & CPC Calculator

TN-S and TN-C-S loop impedance, protection threshold and adiabatic CPC area.

Device threshold met

Compared with the pickup for the selected protective device.

Fault loop impedance
1.056 Ω
Earth-fault current
206.91 A
Maximum permissible Zₛ
1.3656 Ω
CPC area at modeled current
1.1379 mm²

Inputs

Circuit return path
V
×
Ω
Ω
Ω
×
Protection and CPC
A
s
A√s/mm²
Use the value for the material, insulation and starting temperature.

Phase-to-PE fault loop

Live schematic
Loop Zs1.056 ΩFault current206.9 AZs limit1.366 ΩCPC area1.138 mm²TN-S · METALLIC LOOPR₁ phase 0.336 ΩR₂ protective 0.42 ΩEarthed sourceFaulted loadZₑ 0.3 ΩPROTECTIVE DEVICE CHECKProspective earth-fault current206.9 ADevice threshold160 ALoop impedance headroom0.3096 ΩLoop impedance / limit77.33%
The fault returns on PE and, in TN-C-S, through the upstream PEN. The parallel earth paths are omitted.

Derived values & comparisons
Protective device threshold160 A
Zₛ headroom0.30963 Ω
Fault current above threshold46.913 A
Warm phase / CPC resistance0.336 Ω / 0.42 Ω
Next size for modeled fault duty1.5 mm²
Supply voltage after cₘᵢₙ218.5 V

Screening scope. Verify actual loop impedance, the manufacturer’s clearing curve and device breaking capacity. Size the CPC for worst-case let-through I²t and the applicable minimum area. NEC 250 uses separate bonding and equipment grounding provisions.

Calculation method

IEC 60364-4-41 and IEC 60364-5-54. Zₛ = Zₑ + (R₁ + R₂) × temperature factor, with the floor current Iₑꜰ = U₀cₘᵢₙ/Zₛ and limit Zₛ,ₘₐₓ = U₀cₘᵢₙ/Iₐ. Resistances are added as a scalar screening approximation.

The B, C and D defaults use 5, 10 and 20 times In, respectively. For a gG fuse, enter the total-clearing current read from the manufacturer’s curve at the entered time. Use the manufacturer’s curve to determine disconnection time.

The adiabatic calculation is S = Iₑꜰ√t/k for the entered duty. Check the maximum relevant I²t and the applicable mechanical minimum separately. NEC Article 250 describes the effective ground-fault current path and has its own conductor sizing requirements.

Standards and model assumptions