GroundGridLab · IEEE 80-2013
Step & Touch Voltage Calculator
Permissible voltage for a person standing on soil or a surface layer during an AC ground fault.
Step & touch limits met. Both candidate voltages are within the selected exposure limits.
- Permissible touch
- 680.8 V
- Permissible step
- 2,231.1 V
- Surface factor Cₛ
- 0.7
- Clearing headroom
- 1.1049 s
Inputs
| Body weight model | 50 kg / 110 lb |
|---|---|
| Shock / clearing duration | 0.5 s |
| Native soil resistivity | 100 Ω·m |
| Surface layer thickness | 100 mm |
| Surface material resistivity | 3,000 Ω·m |
| Mesh / touch voltage | 380 V |
| Step voltage | 700 V |
Derived values
| Touch comparison at 50 kg | Pass |
|---|---|
| Step comparison at 50 kg | Pass |
| Effective contact resistivity | 2,100 Ω·m |
| Allowable body current | 164.05 mA |
| Maximum clearing duration in model range | 1.605 s |
| 50 kg touch / step | 680.8 V / 2,231 V |
| 70 kg touch / step | 921.4 V / 3,020 V |
Use the worse site conditions and the appropriate body-weight criterion. This screen covers 0.03–3 s power-frequency exposure and excludes transferred or metal-to-metal touch voltage.