GroundGridLab · IEEE 81 · four-point methods
Shallow Wenner pins
Four evenly spaced pins give an example meter reading at 3 m spacing. The assumed deep soil is more conductive than the surface layer.
Resistivity falls with spacing. The trend follows the two assumed layers. The field reading is a separate apparent resistivity.
- Measured apparent ρₐ
- 159.03 Ω·m
- Model at field spacing
- 115.31 Ω·m
- Reflection factor K
- -0.48837
- Geometric factor
- 18.932 m
Inputs
| Electrode arrangement | Wenner 4-pin |
|---|---|
| Adjacent / potential pin spacing a | 3 m |
| Wenner pin burial depth b | 0.15 m |
| Measured V / I | 8.4 Ω |
| Upper-layer resistivity | 160 Ω·m |
| Lower-layer resistivity | 55 Ω·m |
| Upper-layer thickness | 2.2 m |
Derived values
| Apparent / predicted ratio | 1.3792 × |
|---|---|
| Model at 0.1× field spacing | 159.86 Ω·m |
| Model at 10× field spacing | 55.471 Ω·m |
| Upper / lower resistivity | 160 Ω·m / 55 Ω·m |
| Wenner depth multiplier | 1.0044 × |
Use a spacing series and independent traverses to estimate the layer parameters. Account for buried metal, moisture and survey uncertainty.