Nominal 25% baffle cut in water service

A triangular bundle uses a nominal 25% segmental cut and a moderate baffle spacing for cooling water.

Segmental baffle cutaway

Aₛ = DₛB(p − Dₒ)/p · Nu = 0.36 Re⁰·⁵⁵ Pr¹ᐟ³ (μ/μwall)⁰·¹⁴

Edit inputs ↓
Crossflow area
0.02806m²
Shell velocity
1.1404m/s
Shell hₒ
6,681.5W/(m²·K)
Shell ΔP
151.31kPa
Segmental baffle cutawaySHELL INLET →SEGMENTAL CUT19 baffles25 % of shell IDB/Dₛ 0Spacing windowB/Dₛ 1.35
The baffle cut sets the drawn window. The spacing marker shows the entered B/Dₛ compared with the screening band.
  • Within the displayed screening checks.

Inputs

m
m
%
m
L/min
kg/m³
mPa·s
mPa·s
W/(m·K)
kJ/(kg·K)

Calculated results

Bundle crossflow area
0.02806 m²
Crossflow velocity
1.1404 m/s
Shell-side film hₒ
6,681.5 W/(m²·K)
Shell-side pressure drop
151.31 kPa
Equivalent diameter
13.771 mm
Shell Reynolds number
21,011
Gross baffle window
0.057135 m²
Estimated segmental baffles
19
Crossflow sections
20
Shell mass flux
1,129 kg/(m²·s)
Prandtl number
4.989
Kern friction factor
0.26847
Baffle spacing / shell ID
0.37705
Screening minimum spacing
0.122 m

Worked solution

Preset calculation · Metric SI

  1. From the shell bore, spacing, and clear pitch, find 0.02806 m² available for crossflow.
  2. Use the pitch cell to obtain a hydraulic equivalent diameter of 13.771 mm and Reynolds number of 21,011.
  3. Apply the Kern screen across 20 sections to estimate 6,681.5 W/(m²·K) for hₒ and 151.31 kPa for pressure loss.

Check the relationship between equatorial crossflow area, mass flux, and outer film coefficient.

Calculation basis

Kern crossflow area uses the notional tube row at the shell equator. Equivalent diameter comes from the open area and wetted perimeter of a square or triangular pitch cell.

The 25% nominal baffle-cut correlation estimates shell-side hₒ and pressure drop. The entered cut changes the gross segment window and diagram. Leakage, bypass, window obstructions, and nozzle losses require a more detailed method.

The spacing screen runs from the larger of 0.2Dₛ and 50 mm to Dₛ. Maximum unsupported length and vibration depend on the actual tube material and layout.