HeatExchangerLab

Wide baffle cut on a thermal-oil shell

A thermal-oil train has a 35% cut and a substantial bulk-to-wall viscosity change.

Segmental baffle cutaway

Aₛ = DₛB(p − Dₒ)/p · Nu = 0.36 Re⁰·⁵⁵ Pr¹ᐟ³ (μ/μwall)⁰·¹⁴

Edit inputs ↓
Crossflow area
0.057961m²
Shell velocity
1.0007m/s
Shell hₒ
750.81W/(m²·K)
Shell ΔP
98.773kPa
Segmental baffle cutawaySHELL INLET →SEGMENTAL CUT19 baffles35 % of shell IDB/Dₛ 0Spacing windowB/Dₛ 1.35
The baffle cut sets the drawn window. The spacing marker shows the entered B/Dₛ compared with the screening band.
  • Kern coefficients use the nominal 25% cut. The window geometry reflects the entered cut.

Inputs

m
m
%
m
L/min
kg/m³
mPa·s
mPa·s
W/(m·K)
kJ/(kg·K)

Calculated results

Bundle crossflow area
0.057961 m²
Crossflow velocity
1.0007 m/s
Shell-side film hₒ
750.81 W/(m²·K)
Shell-side pressure drop
98.773 kPa
Equivalent diameter
24.142 mm
Shell Reynolds number
4,018.2
Gross baffle window
0.13055 m²
Estimated segmental baffles
19
Crossflow sections
20
Shell mass flux
815.55 kg/(m²·s)
Prandtl number
84.808
Kern friction factor
0.36761
Baffle spacing / shell ID
0.43836
Screening minimum spacing
0.146 m

Worked solution

Preset calculation · Metric SI

  1. From the shell bore, spacing, and clear pitch, find 0.057961 m² available for crossflow.
  2. Use the pitch cell to obtain a hydraulic equivalent diameter of 24.142 mm and Reynolds number of 4,018.2.
  3. Apply the Kern screen across 20 sections to estimate 750.81 W/(m²·K) for hₒ and 98.773 kPa for pressure loss.

Compare the gross window to the crossflow area. The Kern pressure and heat-transfer screen retains its nominal cut basis.

Calculation basis

Kern crossflow area uses the notional tube row at the shell equator. Equivalent diameter comes from the open area and wetted perimeter of a square or triangular pitch cell.

The 25% nominal baffle-cut correlation estimates shell-side hₒ and pressure drop. The entered cut changes the gross segment window and diagram. Leakage, bypass, window obstructions, and nozzle losses require a more detailed method.

The spacing screen runs from the larger of 0.2Dₛ and 50 mm to Dₛ. Maximum unsupported length and vibration depend on the actual tube material and layout.

Methodology and references