Nominal 25% baffle cut in water service
A triangular bundle uses a nominal 25% segmental cut and a moderate baffle spacing for cooling water.
Segmental baffle cutaway
Aₛ = DₛB(p − Dₒ)/p · Nu = 0.36 Re⁰·⁵⁵ Pr¹ᐟ³ (μ/μwall)⁰·¹⁴
- Crossflow area
- 0.02806m²
- Shell velocity
- 1.1404m/s
- Shell hₒ
- 6,681.5W/(m²·K)
- Shell ΔP
- 151.31kPa
- Within the displayed screening checks.
Inputs
Calculated results
- Bundle crossflow area
- 0.02806 m²
- Crossflow velocity
- 1.1404 m/s
- Shell-side film hₒ
- 6,681.5 W/(m²·K)
- Shell-side pressure drop
- 151.31 kPa
- Equivalent diameter
- 13.771 mm
- Shell Reynolds number
- 21,011
- Gross baffle window
- 0.057135 m²
- Estimated segmental baffles
- 19
- Crossflow sections
- 20
- Shell mass flux
- 1,129 kg/(m²·s)
- Prandtl number
- 4.989
- Kern friction factor
- 0.26847
- Baffle spacing / shell ID
- 0.37705
- Screening minimum spacing
- 0.122 m
Worked solution
Preset calculation · Metric SI
- From the shell bore, spacing, and clear pitch, find 0.02806 m² available for crossflow.
- Use the pitch cell to obtain a hydraulic equivalent diameter of 13.771 mm and Reynolds number of 21,011.
- Apply the Kern screen across 20 sections to estimate 6,681.5 W/(m²·K) for hₒ and 151.31 kPa for pressure loss.
Check the relationship between equatorial crossflow area, mass flux, and outer film coefficient.
Calculation basis
Kern crossflow area uses the notional tube row at the shell equator. Equivalent diameter comes from the open area and wetted perimeter of a square or triangular pitch cell.
The 25% nominal baffle-cut correlation estimates shell-side hₒ and pressure drop. The entered cut changes the gross segment window and diagram. Leakage, bypass, window obstructions, and nozzle losses require a more detailed method.
The spacing screen runs from the larger of 0.2Dₛ and 50 mm to Dₛ. Maximum unsupported length and vibration depend on the actual tube material and layout.
Methodology and references