Large-bore thin-wall cooling-water tubes
A cooling-water retrofit evaluates a thin-wall, one-inch tube option at the same outside area.
Tube bundle and pass routing
ΔP = [f × (L/Dᵢ) × nₚ + 4(nₚ − 1)] × ρv²/2
- Required tubes
- 244
- Tube velocity
- 0.91646m/s
- Tube ΔP
- 6.9782kPa
- Reynolds
- 26.27K
- Within the displayed screening checks.
Inputs
Calculated results
- Required tubes
- 244
- Tube velocity
- 0.91646 m/s
- Tube-side pressure drop
- 6.9782 kPa
- Tube Reynolds number
- 26,269
- Estimated tubes that fit
- 438
- Tubes per pass
- 122
- Installed outside area
- 118.77 m²
- Tube inside diameter
- 23.622 mm
- Tube center pitch
- 31.75 mm
- Straight tube loss
- 5.3069 kPa
- Return pass loss
- 1.6714 kPa
- Darcy friction factor
- 0.024591
Worked solution
Preset calculation · Metric SI
- Divide the required area by the area per tube and round up to a complete pass grouping. The result is 244 tubes.
- Put the flow through 122 tubes per pass. The resulting tube speed and Reynolds number are 0.91646 m/s and 26,269.
- Add 5.3069 kPa of straight loss and 1.6714 kPa of return loss.
Compare 20 BWG with 14 BWG. Inside diameter changes velocity and pressure loss while outside area per tube stays the same.
Calculation basis
Required outside area divided by πDₒL gives the raw tube count. Round up to fill complete passes. Bundle capacity counts centers on the selected pitch lattice inside a circular limit after bundle clearance.
The bundle screen uses a centered lattice and omits pass-partition lanes, tie rods, and detailed tubesheet constraints. Confirm actual tube count with a layout drawing.
Straight loss uses Darcy–Weisbach with 64/Re for laminar flow and Haaland for turbulent flow. Add K = 4 per return pass. The default 0.9–2.4 m/s screening band is for initial liquid-service review.
Methodology and references