Six-pass high-velocity water circuit
A six-pass circuit increases water velocity using fewer parallel tubes per pass.
Tube bundle and pass routing
ΔP = [f × (L/Dᵢ) × nₚ + 4(nₚ − 1)] × ρv²/2
- Required tubes
- 276
- Tube velocity
- 3.2295m/s
- Tube ΔP
- 262.52kPa
- Reynolds
- 77.12K
- Tube velocity is above the 2.4 m/s erosion screen.
Inputs
Calculated results
- Required tubes
- 276
- Tube velocity
- 3.2295 m/s
- Tube-side pressure drop
- 262.52 kPa
- Tube Reynolds number
- 77,125
- Estimated tubes that fit
- 462
- Tubes per pass
- 46
- Installed outside area
- 62.768 m²
- Tube inside diameter
- 16.561 mm
- Tube center pitch
- 23.812 mm
- Straight tube loss
- 158.74 kPa
- Return pass loss
- 103.78 kPa
- Darcy friction factor
- 0.022221
Worked solution
Preset calculation · Metric SI
- Divide the required area by the area per tube and round up to a complete pass grouping. The result is 276 tubes.
- Put the flow through 46 tubes per pass. The resulting tube speed and Reynolds number are 3.2295 m/s and 77,125.
- Add 158.74 kPa of straight loss and 103.78 kPa of return loss.
Watch the liquid velocity band and separate friction from return losses. Decreasing the pass count can reduce both substantially.
Calculation basis
Required outside area divided by πDₒL gives the raw tube count. Round up to fill complete passes. Bundle capacity counts centers on the selected pitch lattice inside a circular limit after bundle clearance.
The bundle screen uses a centered lattice and omits pass-partition lanes, tie rods, and detailed tubesheet constraints. Confirm actual tube count with a layout drawing.
Straight loss uses Darcy–Weisbach with 64/Re for laminar flow and Haaland for turbulent flow. Add K = 4 per return pass. The default 0.9–2.4 m/s screening band is for initial liquid-service review.
Methodology and references