Solar Pool Collector Area for a Windy Yard
See how water-level wind and cover hours can change solar collector area for an exposed outdoor pool.
Inputs
Results ↓Results
Example estimate- Collector area in metric
- 107.1 m²
- Collector-to-pool surface ratio
- 230.6 %
- Collector area to maintain target
- 1,102.3 ft²
- Whole-pool warm-up energy
- 1,050,840 BTU
- Daily load during warm-up
- 954,999 BTU/day
- Daily loss at target
- 912,894 BTU/day
- Required heat pump output
- 79,583 BTU/h
- Entered heat pump warm-up time
- 1.83 days
- Heat pump running time
- 21.9 hours
- Water temperature target
- 80 °F
- The model assumes steady average weather and omits direct sunshine into the pool and ground losses. Compare against local collector output.
- Evaporation is highly sensitive to water-level wind. The outdoor wind adjustment is a rough screening estimate.
Calculation inputs
- Pool water surface area
- 500 ft²
- Pool volume
- 18000 US gal
- Starting water temperature
- 73 °F
- Desired temperature increase
- 7 °F
- Desired heat-up time
- 5 days
- Average outdoor air temperature
- 69 °F
- Outdoor relative humidity
- 50 %
- Wind at water surface
- 6 mph
- Solar blanket use
- 10 h/day
- Covered evaporation reduction
- 90 %
- Peak sun hours at the collectors
- 4.75 h/day
- Net useful collector efficiency
- 55 %
- Heat pump output at site conditions
- 110000 BTU/h
- Available heat pump run time
- 12 h/day
Worked example
An exposed pool has higher modeled evaporation than a sheltered pool at the same temperature and RH. Compare 6 mph with 2 mph at water level and look at collector area as well as the heat-loss breakdown.
Suggested solar collector area 1,153.2 ft²
What to check next
Check actual wind across the water rather than relying on an airport reading. Treat higher-wind results as screening estimates and compare several typical nights.
Formulas and assumptions
- Warm-up energy
- BTU = 8.34 × US gallons × temperature rise in °F. Divide by the desired heat-up days and add average daily losses.
- Surface loss
- The air-speed evaporation correlation uses water area, vapor-pressure difference and water-level wind. Blanket use reduces evaporation during covered hours. Surface-only losses use a simple temperature-difference allowance.
- Collector and heat pump
- Size from the larger of the average warm-up load and the target-temperature daily loss. Collector ft² = design daily BTU ÷ useful BTU per ft² per day. Heat pump BTU/h = design daily BTU ÷ run hours.
Frequently asked questions
Where should I measure wind for an outdoor solar pool estimate?
Use representative airspeed close to the water surface. Fences, buildings and landscaping affect the air that reaches the pool.
Can a windbreak change solar pool collector sizing?
It can reduce evaporation by lowering surface wind. Account for any new shading on the pool or collectors before judging the net effect.