Tankless Water Heater GPM & BTU Calculator
Add simultaneous hot-water fixtures, estimate winter temperature rise, and compare tankless gas input with electric kW, current and circuit load.
Inputs
Results ↓Results
Example estimate- Winter inlet temperature
- 48 °F
- Required temperature rise
- 72 °F
- Useful heat into water
- 165,600 BTU/h
- Gas input at steady efficiency
- 176,170 BTU/h
- Electric input
- 49.02 kW
- Total operating current
- 204.3 A
- Operating current per circuit
- 68.1 A
- Breaker comparison per circuit
- 70 A
- Use the manufacturer’s flow-at-rise chart and listed circuit schedule. Breaker figures here are only comparisons.
Calculation inputs
- Showers in use
- 2
- Showers hot-side flow each
- 2 GPM
- Dishwasher in use
- 0
- Dishwasher hot-side flow each
- 1 GPM
- Clothes washer in use
- 0
- Clothes washer hot-side flow each
- 1.5 GPM
- Faucets in use
- 1
- Faucets hot-side flow each
- 0.6 GPM
- Winter groundwater example
- Cool US / southern Canada example
- Target heater outlet temperature
- 120 °F
- Gas efficiency basis
- Steady-state thermal efficiency
- Gas efficiency value
- 94 %
- Electric heating efficiency
- 99 %
- Electric supply voltage
- 240 V
- Equal electric circuits for comparison
- 3
Worked example
Two showers and a faucet use 4.6 GPM of hot water in this example. A 48°F inlet and a 120°F outlet require a 72°F rise during that simultaneous draw.
Peak hot-side demand 4.6 GPM
Formulas and assumptions
- Fixture flow
- Peak hot-side GPM = Σ(simultaneous fixture count × hot-side GPM each). Temperature rise = heater outlet minus winter inlet.
- Heater input
- Heat delivered to water ≈ 500 × GPM × rise in °F. Divide by steady gas efficiency for burner input, or by 3,412.14 and electric efficiency for electric kW.
- Circuit comparison
- Amps = kW × 1,000 ÷ volts for the single-phase example. Split equally among the assumed circuits and compare with the next standard breaker size. Use the manufacturer’s circuit schedule for installation.
Frequently asked questions
Should I use total shower flow or hot-side flow to size a tankless heater?
Use only the portion delivered by the heater. If a shower mixes hot and cold water, its hot fraction is (mixed temperature − inlet temperature) ÷ (heater outlet − inlet temperature).
Why can the same tankless heater deliver fewer GPM in winter?
Cold inlet water requires a larger temperature rise. The same power transfers less hot water per minute at a greater rise.
Can UEF stand in for a tankless heater’s peak thermal efficiency?
UEF describes a test-cycle result. A UEF-based input here is an optional screening comparison. Confirm peak flow and burner input from the model’s performance chart.