Deep-plan studio window

Explore how a small amount of glazing in a deep room lowers average daylight even with bright outdoor overcast illuminance.

Room and window
ft
ft
ft
ft²
°
Surfaces and sky
fc
Daylight DF
1.04%
Interior avg.
14.48fc
Glazing/floor
6.25%
Bounding area
3,039.7ft²

Window and visible sky section

Edit inputs ↓
Window and visible sky sectionOVERCAST SKYWINDOW SECTIONθ 54°T 0.6Glass 51.67 ft²Average interior daylight14.48 fc
The sky angle is the unobstructed vertical sky seen from the glazing, measured in degrees.

Daylight adequacy

Review needed
OutsideThresholdWithin
  • Lower daylight band1.04 / ≥ 2 % outside screen
  • Upper daylight band1.04 / ≤ 5 % within screen

Below 2% · low daylight

Additional readings
Room floor area826.67ft²
Total wall area1,386.39ft²
Horizontal overcast illuminance1,393.55fc
Daylight screening tierBelow 2% · low daylight

Worked calculation

US customary results for the original preset.

  1. Add the floor, ceiling, and four walls to get a bounding surface area of 3039.7 ft².
  2. Combine 51.67 ft² of glazing, transmittance 0.6, and 54 ° of visible sky. The simplified DF is 1.04 %.
  3. Multiply 1393.55 fc outside by DF/100 to get 14.48 fc average inside. The window-to-floor ratio is 6.25 %.

Calculation method

This simplified split-flux screen uses 1 − Ravg. The published BRE average daylight factor equation uses 1 − Ravg².

Bounding area
Atot = 2(LW + LH + WH)
Simplified daylight factor
DF (%) = T × Aw × θ/[Atot × (1 − Ravg)]
Interior daylight and glazing ratio
Einside = Eovercast × DF/100 · WFR (%) = 100Aw/(LW)

Use climate-based daylight modeling for certification and a luminance-based analysis for glare. High reflectance can amplify this estimate.

Sources and assumptions ↗