Deep-plan studio window
Explore how a small amount of glazing in a deep room lowers average daylight even with bright outdoor overcast illuminance.
Inputs
View results ↑- Daylight DF
- 1.04%
- Interior avg.
- 14.48fc
- Glazing/floor
- 6.25%
- Bounding area
- 3,039.7ft²
Window and visible sky section
Edit inputs ↓Daylight adequacy
Review neededOutsideThresholdWithin
- Lower daylight band1.04 / ≥ 2 % outside screen
- Upper daylight band1.04 / ≤ 5 % within screen
Below 2% · low daylight
Additional readings
| Room floor area | 826.67ft² |
|---|---|
| Total wall area | 1,386.39ft² |
| Horizontal overcast illuminance | 1,393.55fc |
| Daylight screening tier | Below 2% · low daylight |
Worked calculation
US customary results for the original preset.
- Add the floor, ceiling, and four walls to get a bounding surface area of 3039.7 ft².
- Combine 51.67 ft² of glazing, transmittance 0.6, and 54 ° of visible sky. The simplified DF is 1.04 %.
- Multiply 1393.55 fc outside by DF/100 to get 14.48 fc average inside. The window-to-floor ratio is 6.25 %.
Calculation method
This simplified split-flux screen uses 1 − Ravg. The published BRE average daylight factor equation uses 1 − Ravg².
- Bounding area
- Atot = 2(LW + LH + WH)
- Simplified daylight factor
- DF (%) = T × Aw × θ/[Atot × (1 − Ravg)]
- Interior daylight and glazing ratio
- Einside = Eovercast × DF/100 · WFR (%) = 100Aw/(LW)
Use climate-based daylight modeling for certification and a luminance-based analysis for glare. High reflectance can amplify this estimate.
Sources and assumptions ↗LightingLuxLab · US customary
Deep-plan studio window
Inputs
| Room length | 39.3700787ft |
|---|---|
| Room width | 20.9973753ft |
| Room height | 11.4829396ft |
| Net glazed area | 51.66677ft² |
| Visible transmittance | 0.6 |
| Visible sky angle | 54° |
| Mean surface reflectance | 0.47 |
| Outdoor overcast illuminance | 1,393.5456fc |
Results
| Daylight DF | 1.04% |
|---|---|
| Interior avg. | 14.48fc |
| Glazing/floor | 6.25% |
| Bounding area | 3,039.7ft² |
| Room floor area | 826.67ft² |
| Total wall area | 1,386.39ft² |
| Horizontal overcast illuminance | 1,393.55fc |
| Daylight screening tier | Below 2% · low daylight |
Daylight adequacy
- Lower daylight band · 1.04 / ≥ 2 % · Outside screen
- Upper daylight band · 1.04 / ≤ 5 % · Within screen
Below 2% · low daylight
Use climate-based daylight modeling for certification and a luminance-based analysis for glare. High reflectance can amplify this estimate.