Diffusing-glass workshop

Compare a large area of diffusing glass with lower visible transmittance in a tall industrial room.

Room and window
ft
ft
ft
ft²
°
Surfaces and sky
fc
Daylight DF
5.49%
Interior avg.
43.35fc
Glazing/floor
25.81%
Bounding area
5,401.3ft²

Window and visible sky section

Edit inputs ↓
Window and visible sky sectionOVERCAST SKYWINDOW SECTIONθ 65°T 0.49Glass 344.45 ft²Average interior daylight43.35 fc
The sky angle is the unobstructed vertical sky seen from the glazing, measured in degrees.

Daylight adequacy

Review needed
OutsideThresholdWithin
  • Lower daylight band5.49 / ≥ 2 % within screen
  • Upper daylight band5.49 / ≤ 5 % outside screen

Above 5% · glare risk screen

Additional readings
Room floor area1,334.72ft²
Total wall area2,731.88ft²
Horizontal overcast illuminance789.68fc
Daylight screening tierAbove 5% · glare risk screen

Worked calculation

US customary results for the original preset.

  1. Add the floor, ceiling, and four walls to get a bounding surface area of 5401.3 ft².
  2. Combine 344.45 ft² of glazing, transmittance 0.49, and 65 ° of visible sky. The simplified DF is 5.49 %.
  3. Multiply 789.68 fc outside by DF/100 to get 43.35 fc average inside. The window-to-floor ratio is 25.81 %.

Calculation method

This simplified split-flux screen uses 1 − Ravg. The published BRE average daylight factor equation uses 1 − Ravg².

Bounding area
Atot = 2(LW + LH + WH)
Simplified daylight factor
DF (%) = T × Aw × θ/[Atot × (1 − Ravg)]
Interior daylight and glazing ratio
Einside = Eovercast × DF/100 · WFR (%) = 100Aw/(LW)

Use climate-based daylight modeling for certification and a luminance-based analysis for glare. High reflectance can amplify this estimate.

Sources and assumptions ↗