Distribution center packing room
Compare a high light level for packing benches with the output of an industrial fixture. A larger LDD reserve accounts for the dirtier environment.
Inputs
View results ↑- Fixture grid
- 6 × 3
- Maintained
- 38.39fc
- Cavity ratio
- 2.95
- Connected
- 2,376W
Room section and fixture plan
Edit inputs ↓IES layout screen
Within screen- Maintained target38.39 / ≥ 35 fc within screen
- Spacing / mounting height0.95 / ≤ 1.35 × within screen
Checks compare maintained average and the entered spacing criterion.
Additional readings
| Floor area | 4,320ft² |
|---|---|
| Room cavity height | 19ft |
| Combined light loss factor | 0.688 |
| Maintained lumens per fixture | 9,214.54lm |
| Calculated fractional fixture count | 16.4089 |
| Minimum whole fixture count | 17 |
| Fixtures in rectangular grid | 18 |
| Lengthwise pitch | 13.33ft |
| Crosswise pitch | 18ft |
| Largest pitch / mounting height | 0.947× |
| Pitch limit from spacing criterion | 25.65ft |
Worked calculation
US customary results for the original preset.
- Use the room section to get a cavity height of 19 ft and an RCR of 2.947.
- Multiply 18100 lm by CU 0.74 and LLF 0.688 to get 9214.54 lm maintained per fixture.
- Round 16.4089 up to 17. The 6 × 3 grid supplies 38.39 fc on average.
Calculation method
Calculate the room cavity ratio from the room, workplane, and fixture heights. Use the utilization factor at that RCR and surface reflectance. Pair absolute luminaire lumens with room utilization (utilance). Pair relative lamp lumens with published CU and ballast factor.
- Room cavity ratio
- hᵣ꜀ = H − hwp − hcc · RCR = 5hᵣ꜀(L + W)/(LW)
- Maintained lumens per fixture
- Φmaintained = Φ × CU × LLD × LDD × BF
- Fixture count and pitch
- N = Etarget × LW/Φmaintained · Sx = L/Nx · Sy = W/Ny
Verify point illuminance, glare and uniformity with fixture photometry. The manufacturer’s spacing criterion is a layout screen.
Sources and assumptions ↗Distribution center packing room
Inputs
| Room length | 80ft |
|---|---|
| Room width | 54ft |
| Ceiling height | 24ft |
| Workplane height | 3ft |
| Fixture suspension | 2ft |
| Output per fixture | 18,100lm |
| Utilization (CU) | 0.74 |
| Lumen depreciation (LLD) | 0.9 |
| Dirt depreciation (LDD) | 0.78 |
| Ballast factor (BF) | 0.98 |
| Target illuminance | 35fc |
| Max spacing / height | 1.35× |
| Input per fixture | 132W |
Results
| Fixture grid | 6 × 3 |
|---|---|
| Maintained | 38.39fc |
| Cavity ratio | 2.95 |
| Connected | 2,376W |
| Floor area | 4,320ft² |
| Room cavity height | 19ft |
| Combined light loss factor | 0.688 |
| Maintained lumens per fixture | 9,214.54lm |
| Calculated fractional fixture count | 16.4089 |
| Minimum whole fixture count | 17 |
| Fixtures in rectangular grid | 18 |
| Lengthwise pitch | 13.33ft |
| Crosswise pitch | 18ft |
| Largest pitch / mounting height | 0.947× |
| Pitch limit from spacing criterion | 25.65ft |
IES layout screen
- Maintained target · 38.39 / ≥ 35 fc · Within screen
- Spacing / mounting height · 0.95 / ≤ 1.35 × · Within screen
Checks compare maintained average and the entered spacing criterion.
Verify point illuminance, glare and uniformity with fixture photometry. The manufacturer’s spacing criterion is a layout screen.