Lumen Method Calculator

Size a fixture grid for maintained workplane illuminance using the IES zonal cavity method.

Room geometry
ft
ft
ft
ft
ft
Luminaire and target
lm
fc
×
W
Fixture grid
6 × 3
Maintained
36.47fc
Cavity ratio
3.04
Connected
612W

Room section and fixture plan

Edit inputs ↓
Room section and fixture planROOM SECTIONFIXTURE PLANCavity 10 ft6 × 3 GRIDMaintained workplane36.47 fc
The grid uses equal pitch with half-pitch offsets at the walls.

IES layout screen

Within screen
OutsideThresholdWithin
  • Maintained target36.47 / ≥ 35 fc within screen
  • Spacing / mounting height0.93 / ≤ 1.35 × within screen

Checks compare maintained average and the entered spacing criterion.

Additional readings
Floor area1,120ft²
Room cavity height10ft
Combined light loss factor0.7585
Maintained lumens per fixture2,269.49lm
Calculated fractional fixture count17.2726
Minimum whole fixture count18
Fixtures in rectangular grid18
Lengthwise pitch6.67ft
Crosswise pitch9.33ft
Largest pitch / mounting height0.933×
Pitch limit from spacing criterion13.5ft

Calculation method

Calculate the room cavity ratio from the room, workplane, and fixture heights. Use the utilization factor at that RCR and surface reflectance. Pair absolute luminaire lumens with room utilization (utilance). Pair relative lamp lumens with published CU and ballast factor.

Room cavity ratio
hᵣ꜀ = H − hwp − hcc · RCR = 5hᵣ꜀(L + W)/(LW)
Maintained lumens per fixture
Φmaintained = Φ × CU × LLD × LDD × BF
Fixture count and pitch
N = Etarget × LW/Φmaintained · Sx = L/Nx · Sy = W/Ny

Verify point illuminance, glare and uniformity with fixture photometry. The manufacturer’s spacing criterion is a layout screen.

Sources and assumptions ↗