Elevated machine workplane
Set the luminaire plane at the same height as the modeled workplane to see how the zero-cavity boundary disables the spacing ratio.
Inputs
View results ↑- Fixture grid
- 2 × 2
- Maintained
- 32.04fc
- Cavity ratio
- 0
- Connected
- 136W
Room section and fixture plan
Edit inputs ↓IES layout screen
Review needed- Maintained target32.04 / ≥ 18.58 fc within screen
- Spacing / mounting height— / ≤ 1.35 × outside screen
Zero cavity height leaves no usable mounting height for the spacing check.
Additional readings
| Floor area | 129.17ft² |
|---|---|
| Room cavity height | 0ft |
| Combined light loss factor | 0.7585 |
| Maintained lumens per fixture | 1,034.62lm |
| Calculated fractional fixture count | 2.3197 |
| Minimum whole fixture count | 3 |
| Fixtures in rectangular grid | 4 |
| Lengthwise pitch | 6.56ft |
| Crosswise pitch | 4.92ft |
| Largest pitch / mounting height | — |
| Pitch limit from spacing criterion | 0ft |
Worked calculation
US customary results for the original preset.
- Use the room section to get a cavity height of 0 ft and an RCR of 0.
- Multiply 2200 lm by CU 0.62 and LLF 0.7585 to get 1034.62 lm maintained per fixture.
- Round 2.3197 up to 3. The 2 × 2 grid supplies 32.04 fc on average.
Calculation method
Calculate the room cavity ratio from the room, workplane, and fixture heights. Use the utilization factor at that RCR and surface reflectance. Pair absolute luminaire lumens with room utilization (utilance). Pair relative lamp lumens with published CU and ballast factor.
- Room cavity ratio
- hᵣ꜀ = H − hwp − hcc · RCR = 5hᵣ꜀(L + W)/(LW)
- Maintained lumens per fixture
- Φmaintained = Φ × CU × LLD × LDD × BF
- Fixture count and pitch
- N = Etarget × LW/Φmaintained · Sx = L/Nx · Sy = W/Ny
Verify point illuminance, glare and uniformity with fixture photometry. The manufacturer’s spacing criterion is a layout screen.
Sources and assumptions ↗Elevated machine workplane
Inputs
| Room length | 13.1233596ft |
|---|---|
| Room width | 9.8425197ft |
| Ceiling height | 9.8425197ft |
| Workplane height | 8.2020997ft |
| Fixture suspension | 1.6404199ft |
| Output per fixture | 2,200lm |
| Utilization (CU) | 0.62 |
| Lumen depreciation (LLD) | 0.9 |
| Dirt depreciation (LDD) | 0.86 |
| Ballast factor (BF) | 0.98 |
| Target illuminance | 18.580608fc |
| Max spacing / height | 1.35× |
| Input per fixture | 34W |
Results
| Fixture grid | 2 × 2 |
|---|---|
| Maintained | 32.04fc |
| Cavity ratio | 0 |
| Connected | 136W |
| Floor area | 129.17ft² |
| Room cavity height | 0ft |
| Combined light loss factor | 0.7585 |
| Maintained lumens per fixture | 1,034.62lm |
| Calculated fractional fixture count | 2.3197 |
| Minimum whole fixture count | 3 |
| Fixtures in rectangular grid | 4 |
| Lengthwise pitch | 6.56ft |
| Crosswise pitch | 4.92ft |
| Largest pitch / mounting height | — |
| Pitch limit from spacing criterion | 0ft |
IES layout screen
- Maintained target · 32.04 / ≥ 18.58 fc · Within screen
- Spacing / mounting height · — / ≤ 1.35 × · Outside screen
Zero cavity height leaves no usable mounting height for the spacing check.
Verify point illuminance, glare and uniformity with fixture photometry. The manufacturer’s spacing criterion is a layout screen.