School library reading room
Plan an equal-pitch layout above shared reading tables using recessed panels and an elevated workplane.
Inputs
View results ↑- Fixture grid
- 7 × 4
- Maintained
- 32.29fc
- Cavity ratio
- 2.07
- Connected
- 840W
Room section and fixture plan
Edit inputs ↓IES layout screen
Within screen- Maintained target32.29 / ≥ 32 fc within screen
- Spacing / mounting height1 / ≤ 1.35 × within screen
Checks compare maintained average and the entered spacing criterion.
Additional readings
| Floor area | 1,768ft² |
|---|---|
| Room cavity height | 8.5ft |
| Combined light loss factor | 0.7585 |
| Maintained lumens per fixture | 2,038.9lm |
| Calculated fractional fixture count | 27.7483 |
| Minimum whole fixture count | 28 |
| Fixtures in rectangular grid | 28 |
| Lengthwise pitch | 7.43ft |
| Crosswise pitch | 8.5ft |
| Largest pitch / mounting height | 1× |
| Pitch limit from spacing criterion | 11.48ft |
Worked calculation
US customary results for the original preset.
- Use the room section to get a cavity height of 8.5 ft and an RCR of 2.067.
- Multiply 4200 lm by CU 0.64 and LLF 0.7585 to get 2038.9 lm maintained per fixture.
- Round 27.7483 up to 28. The 7 × 4 grid supplies 32.29 fc on average.
Calculation method
Calculate the room cavity ratio from the room, workplane, and fixture heights. Use the utilization factor at that RCR and surface reflectance. Pair absolute luminaire lumens with room utilization (utilance). Pair relative lamp lumens with published CU and ballast factor.
- Room cavity ratio
- hᵣ꜀ = H − hwp − hcc · RCR = 5hᵣ꜀(L + W)/(LW)
- Maintained lumens per fixture
- Φmaintained = Φ × CU × LLD × LDD × BF
- Fixture count and pitch
- N = Etarget × LW/Φmaintained · Sx = L/Nx · Sy = W/Ny
Verify point illuminance, glare and uniformity with fixture photometry. The manufacturer’s spacing criterion is a layout screen.
Sources and assumptions ↗School library reading room
Inputs
| Room length | 52ft |
|---|---|
| Room width | 34ft |
| Ceiling height | 11ft |
| Workplane height | 2.5ft |
| Fixture suspension | 0ft |
| Output per fixture | 4,200lm |
| Utilization (CU) | 0.64 |
| Lumen depreciation (LLD) | 0.9 |
| Dirt depreciation (LDD) | 0.86 |
| Ballast factor (BF) | 0.98 |
| Target illuminance | 32fc |
| Max spacing / height | 1.35× |
| Input per fixture | 30W |
Results
| Fixture grid | 7 × 4 |
|---|---|
| Maintained | 32.29fc |
| Cavity ratio | 2.07 |
| Connected | 840W |
| Floor area | 1,768ft² |
| Room cavity height | 8.5ft |
| Combined light loss factor | 0.7585 |
| Maintained lumens per fixture | 2,038.9lm |
| Calculated fractional fixture count | 27.7483 |
| Minimum whole fixture count | 28 |
| Fixtures in rectangular grid | 28 |
| Lengthwise pitch | 7.43ft |
| Crosswise pitch | 8.5ft |
| Largest pitch / mounting height | 1× |
| Pitch limit from spacing criterion | 11.48ft |
IES layout screen
- Maintained target · 32.29 / ≥ 32 fc · Within screen
- Spacing / mounting height · 1 / ≤ 1.35 × · Within screen
Checks compare maintained average and the entered spacing criterion.
Verify point illuminance, glare and uniformity with fixture photometry. The manufacturer’s spacing criterion is a layout screen.