School library reading room

Plan an equal-pitch layout above shared reading tables using recessed panels and an elevated workplane.

Room geometry
ft
ft
ft
ft
ft
Luminaire and target
lm
fc
×
W
Fixture grid
7 × 4
Maintained
32.29fc
Cavity ratio
2.07
Connected
840W

Room section and fixture plan

Edit inputs ↓
Room section and fixture planROOM SECTIONFIXTURE PLANCavity 8.5 ftSample · 7 × 4Maintained workplane32.29 fc
The grid uses equal pitch with half-pitch offsets at the walls.

IES layout screen

Within screen
OutsideThresholdWithin
  • Maintained target32.29 / ≥ 32 fc within screen
  • Spacing / mounting height1 / ≤ 1.35 × within screen

Checks compare maintained average and the entered spacing criterion.

Additional readings
Floor area1,768ft²
Room cavity height8.5ft
Combined light loss factor0.7585
Maintained lumens per fixture2,038.9lm
Calculated fractional fixture count27.7483
Minimum whole fixture count28
Fixtures in rectangular grid28
Lengthwise pitch7.43ft
Crosswise pitch8.5ft
Largest pitch / mounting height1×
Pitch limit from spacing criterion11.48ft

Worked calculation

US customary results for the original preset.

  1. Use the room section to get a cavity height of 8.5 ft and an RCR of 2.067.
  2. Multiply 4200 lm by CU 0.64 and LLF 0.7585 to get 2038.9 lm maintained per fixture.
  3. Round 27.7483 up to 28. The 7 × 4 grid supplies 32.29 fc on average.

Calculation method

Calculate the room cavity ratio from the room, workplane, and fixture heights. Use the utilization factor at that RCR and surface reflectance. Pair absolute luminaire lumens with room utilization (utilance). Pair relative lamp lumens with published CU and ballast factor.

Room cavity ratio
hᵣ꜀ = H − hwp − hcc · RCR = 5hᵣ꜀(L + W)/(LW)
Maintained lumens per fixture
Φmaintained = Φ × CU × LLD × LDD × BF
Fixture count and pitch
N = Etarget × LW/Φmaintained · Sx = L/Nx · Sy = W/Ny

Verify point illuminance, glare and uniformity with fixture photometry. The manufacturer’s spacing criterion is a layout screen.

Sources and assumptions ↗