Distribution center packing room

Compare a high light level for packing benches with the output of an industrial fixture. A larger LDD reserve accounts for the dirtier environment.

Room geometry
ft
ft
ft
ft
ft
Luminaire and target
lm
fc
×
W
Fixture grid
6 × 3
Maintained
38.39fc
Cavity ratio
2.95
Connected
2,376W

Room section and fixture plan

Edit inputs ↓
Room section and fixture planROOM SECTIONFIXTURE PLANCavity 19 ft6 × 3 GRIDMaintained workplane38.39 fc
The grid uses equal pitch with half-pitch offsets at the walls.

IES layout screen

Within screen
OutsideThresholdWithin
  • Maintained target38.39 / ≥ 35 fc within screen
  • Spacing / mounting height0.95 / ≤ 1.35 × within screen

Checks compare maintained average and the entered spacing criterion.

Additional readings
Floor area4,320ft²
Room cavity height19ft
Combined light loss factor0.688
Maintained lumens per fixture9,214.54lm
Calculated fractional fixture count16.4089
Minimum whole fixture count17
Fixtures in rectangular grid18
Lengthwise pitch13.33ft
Crosswise pitch18ft
Largest pitch / mounting height0.947×
Pitch limit from spacing criterion25.65ft

Worked calculation

US customary results for the original preset.

  1. Use the room section to get a cavity height of 19 ft and an RCR of 2.947.
  2. Multiply 18100 lm by CU 0.74 and LLF 0.688 to get 9214.54 lm maintained per fixture.
  3. Round 16.4089 up to 17. The 6 × 3 grid supplies 38.39 fc on average.

Calculation method

Calculate the room cavity ratio from the room, workplane, and fixture heights. Use the utilization factor at that RCR and surface reflectance. Pair absolute luminaire lumens with room utilization (utilance). Pair relative lamp lumens with published CU and ballast factor.

Room cavity ratio
hᵣ꜀ = H − hwp − hcc · RCR = 5hᵣ꜀(L + W)/(LW)
Maintained lumens per fixture
Φmaintained = Φ × CU × LLD × LDD × BF
Fixture count and pitch
N = Etarget × LW/Φmaintained · Sx = L/Nx · Sy = W/Ny

Verify point illuminance, glare and uniformity with fixture photometry. The manufacturer’s spacing criterion is a layout screen.

Sources and assumptions ↗