Matte black receiving panel

Set the ideal diffuse reflectance to zero. Incident illuminance remains positive while estimated surface luminance is zero.

Light source
cd
°
Enter an angle below 180°, or exactly 360° for a full sphere.
W
Receiving surface
ft
fc
Intensity
1,800cd
Beam center
29.03fc
Beam diameter
6.05ft
Luminance
0fL

Solid-angle cone and receiving plane

Edit inputs ↓
Solid-angle cone and receiving planeUNIFORM CONERECEIVING PLANEα 42°Ø 6.05 ftThrow 7.87 ftSolid angle0.417 sr
Cone scale illustrates centerline throw. Full-sphere emission has no finite beam diameter.

Beam center target

Within screen
OutsideThresholdWithin
  • Axial illuminance29.03 / ≥ 27.87 fc within screen

The target applies on the optical axis.

Additional readings
Luminous flux751.19lm
Solid angle0.4173sr
Luminaire efficacy44.19lm/W
Diameter at the receiving plane6.05ft

Worked calculation

US customary results for the original preset.

  1. Convert the full beam angle of 42 ° to 0.4173 sr. The uniform-cone relationship pairs 751.19 lm with 1800 cd.
  2. At a throw of 7.87 ft, the center receives 29.03 fc. The projected cone diameter is 6.05 ft.
  3. Apply diffuse reflectance 0 to estimate 0 fL at the center.

Calculation method

In the uniform-cone approximation the axial intensity equals the average intensity inside the cone. Real FWHM beam distributions need an IES or LDT file.

Beam solid angle and flux
Ω = 2π(1 − cos(α/2)) · Φ = IΩ · Ωsphere = 4π
Beam footprint and center
Diameter = 2d tan(α/2) · Ecenter = I/d²
Diffuse luminance and efficacy
L = Ecenter × ρ/π · efficacy = Φ/W

Use measured photometry for beam edges, off-axis illuminance and non-Lambertian materials.

Sources and assumptions ↗