Two symmetric aisle luminaires

Put the calculation point midway between a matched pair. Both horizontal contributions are equal and both rays use the same directional candela.

Primary ray
cd
ft
ft
ft
Pair and target
ft
Zero uses the primary position only. The second source is at x = spacing.
cd
fc
Horizontal
16.91fc
Radial vert.
11.28fc
Nadir angle
33.7°
Slant distance
17.74ft

Inverse-square ray geometry

Edit inputs ↓
Inverse-square ray geometryRAY SECTIONTWO POSITIONSh 14.76 ftθ 33.7°r 9.84 ftD 17.74 ftHorizontal light16.91 fc
The ray section folds the x and y offsets into radial distance. Vertical readings are radially facing magnitudes.

Horizontal task target

Within screen
OutsideThresholdWithin
  • Direct horizontal light16.91 / ≥ 15.79 fc within screen

Choose a task and a project target appropriate to its IES recommendation.

Additional readings
Primary radial offset9.84ft
Primary horizontal contribution8.46fc
Primary radial vertical contribution5.64fc
Second nadir angle33.7°
Second slant distance17.74ft
Second horizontal contribution8.46fc
Second radial vertical contribution5.64fc

Worked calculation

US customary results for the original preset.

  1. Combine the two offsets to get a radius of 9.84 ft. The primary slant distance is 17.74 ft at 33.7 °.
  2. Project 3200 cd onto the horizontal plane. The primary group contributes 8.46 fc.
  3. Add 8.46 fc from the second group. The radial-facing vertical total is 11.28 fc.

Calculation method

Read candela at the computed nadir and azimuth from the luminaire file. For the second position, use its own directional candela.

Distance and angle
r = √(dx² + dy²) · D = √(r² + h²) · θ = atan2(r, h)
Horizontal and radial vertical light
Eh = I cos³(θ)/h² · Ev = I cos²(θ) sin(θ)/h²
Superposition
Etotal = m × sum of illuminances at the modeled positions

This direct-light screen omits reflections, obstructions and finite luminaire size. Sum projections onto the actual wall normal for a fixed receiving plane.