Two symmetric aisle luminaires
Put the calculation point midway between a matched pair. Both horizontal contributions are equal and both rays use the same directional candela.
Inputs
View results ↑- Horizontal
- 16.91fc
- Radial vert.
- 11.28fc
- Nadir angle
- 33.7°
- Slant distance
- 17.74ft
Inverse-square ray geometry
Edit inputs ↓Horizontal task target
Within screen- Direct horizontal light16.91 / ≥ 15.79 fc within screen
Choose a task and a project target appropriate to its IES recommendation.
Additional readings
| Primary radial offset | 9.84ft |
|---|---|
| Primary horizontal contribution | 8.46fc |
| Primary radial vertical contribution | 5.64fc |
| Second nadir angle | 33.7° |
| Second slant distance | 17.74ft |
| Second horizontal contribution | 8.46fc |
| Second radial vertical contribution | 5.64fc |
Worked calculation
US customary results for the original preset.
- Combine the two offsets to get a radius of 9.84 ft. The primary slant distance is 17.74 ft at 33.7 °.
- Project 3200 cd onto the horizontal plane. The primary group contributes 8.46 fc.
- Add 8.46 fc from the second group. The radial-facing vertical total is 11.28 fc.
Calculation method
Read candela at the computed nadir and azimuth from the luminaire file. For the second position, use its own directional candela.
- Distance and angle
- r = √(dx² + dy²) · D = √(r² + h²) · θ = atan2(r, h)
- Horizontal and radial vertical light
- Eh = I cos³(θ)/h² · Ev = I cos²(θ) sin(θ)/h²
- Superposition
- Etotal = m × sum of illuminances at the modeled positions
This direct-light screen omits reflections, obstructions and finite luminaire size. Sum projections onto the actual wall normal for a fixed receiving plane.
Sources and assumptions ↗Two symmetric aisle luminaires
Inputs
| Directional intensity | 3,200cd |
|---|---|
| Mounting height above point | 14.7637795ft |
| Longitudinal offset | 9.8425197ft |
| Crosswise offset | 0ft |
| Luminaires per position | 1 |
| Second position spacing | 19.6850394ft |
| Second directional intensity | 3,200cd |
| Horizontal target | 15.7935168fc |
Results
| Horizontal | 16.91fc |
|---|---|
| Radial vert. | 11.28fc |
| Nadir angle | 33.7° |
| Slant distance | 17.74ft |
| Primary radial offset | 9.84ft |
| Primary horizontal contribution | 8.46fc |
| Primary radial vertical contribution | 5.64fc |
| Second nadir angle | 33.7° |
| Second slant distance | 17.74ft |
| Second horizontal contribution | 8.46fc |
| Second radial vertical contribution | 5.64fc |
Horizontal task target
- Direct horizontal light · 16.91 / ≥ 15.79 fc · Within screen
Choose a task and a project target appropriate to its IES recommendation.
This direct-light screen omits reflections, obstructions and finite luminaire size. Sum projections onto the actual wall normal for a fixed receiving plane.