Dry Winter Intake Air

Check when cold, dry intake air leaves little or no water for the aftercooler.

Inputs

View results ↓
Intake air
°F
%
SCFM
Cooling and drying
psig
°F
°F
h/day

Results

Edit inputs ↑
Moisture removal from intake to outlet PRESS. DP 39 °FATM. DP -3.146 °FAFTERCOOLER 0 US gal/dayTOTAL DRAIN 0.1026 US gal/day AIRFLOW INTAKE 0.5721 lb/h AFTERCOOLER 0 lb/h DRYER 0.08559 lb/h OUTLET 0.4865 lb/h DRAIN DRAIN INLET WATER REMOVED 14.96 % 0% MASS BALANCE 100%
Moisture removal from intake to outlet
Outlet pressure dew point
39 °F
Atmospheric dew point
-3.1461 °F
Aftercooler liquid drain
0 US gal/day
Total collected liquid
0.10256 US gal/day
Intake saturation vapor pressure
0.073706 psia
Inlet water vapor
0.57213 lb/h
Water removed at aftercooler
0 lb/h
Water removed by dryer
0.085587 lb/h
Outlet water vapor
0.48654 lb/h
Liquid collected at dryer
0.10256 US gal/day
Total removal as liquid equivalent
0.10256 US gal/day

Formula and assumptions

Compute saturation and intake moisture

Psat = 611.2 exp(aT/(b + T)) · w = 0.621945 Pv/(Pabs − Pv)

T is in °C and vapor pressures are in Pa. Magnus uses a = 17.62 and b = 243.12 over water, and 22.46 and 272.62 over ice below freezing. Enter relative humidity with respect to the phase used. The dry-air flow establishes dry-air mass.

Track water through both stages

Water removed = dry-air mass flow × change in humidity ratio

Limit the entering humidity ratio to saturation at each stage’s pressure and target temperature. A refrigerated dryer’s cold separator can drain liquid. A desiccant target is a pressure dew point, and regeneration typically exhausts the removed water as vapor. Drain estimates use about 1 kg of water per liter and the entered daily hours.

Find pressure and atmospheric dew points

Pv,out = Pline × wout/(0.621945 + wout) · Pv,atm = Pv,out × Pₐₜₘ/Pline

Invert the saturation equation at each vapor pressure. Below freezing the result is a frost point. Values below −65 °C extrapolate the ice fit. ISO 8573-1 class verification requires measured air quality at the point of use.

Flow labels use dry gas at 101.325 kPa, with 60 °F for SCFM and 0 °C for normal metric flow. See all unit conventions.

Worked examples