Humid Shop With a Refrigerated Dryer
Follow 200 SCFM of humid intake air through a 95 °F aftercooler and a 3 °C cold separator.
Inputs
View results ↓Results
Edit inputs ↑- Outlet pressure dew point
- 37.4 °F
- Atmospheric dew point
- -5.156 °F
- Aftercooler liquid drain
- 22.187 US gal/day
- Total collected liquid
- 32.326 US gal/day
- Intake saturation vapor pressure
- 0.45833 psia
- Inlet water vapor
- 11.787 lb/h
- Water removed at aftercooler
- 7.7148 lb/h
- Water removed by dryer
- 3.5259 lb/h
- Outlet water vapor
- 0.54629 lb/h
- Liquid collected at dryer
- 10.14 US gal/day
- Total removal as liquid equivalent
- 32.326 US gal/day
Formula and assumptions
Compute saturation and intake moisture
Psat = 611.2 exp(aT/(b + T)) · w = 0.621945 Pv/(Pabs − Pv)
T is in °C and vapor pressures are in Pa. Magnus uses a = 17.62 and b = 243.12 over water, and 22.46 and 272.62 over ice below freezing. Enter relative humidity with respect to the phase used. The dry-air flow establishes dry-air mass.
Track water through both stages
Water removed = dry-air mass flow × change in humidity ratio
Limit the entering humidity ratio to saturation at each stage’s pressure and target temperature. A refrigerated dryer’s cold separator can drain liquid. A desiccant target is a pressure dew point, and regeneration typically exhausts the removed water as vapor. Drain estimates use about 1 kg of water per liter and the entered daily hours.
Find pressure and atmospheric dew points
Pv,out = Pline × wout/(0.621945 + wout) · Pv,atm = Pv,out × Pₐₜₘ/Pline
Invert the saturation equation at each vapor pressure. Below freezing the result is a frost point. Values below −65 °C extrapolate the ice fit. ISO 8573-1 class verification requires measured air quality at the point of use.
Flow labels use dry gas at 101.325 kPa, with 60 °F for SCFM and 0 °C for normal metric flow. See all unit conventions.
Worked examples
-
Humid Shop With a Refrigerated Dryer
Follow 200 SCFM of humid intake air through a 95 °F aftercooler and a 3 °C cold separator.
-
Summer Aftercooler Condensate Load
Estimate condensate for a hot and humid intake on a two-shift, 450 SCFM plant.
-
−40 °C Desiccant Pressure Dew Point
Estimate moisture removed with a −40 °C desiccant target on an industrial dry-air branch.
-
Dry Winter Intake Air
Check when cold, dry intake air leaves little or no water for the aftercooler.
-
Higher-Pressure Process Air
Estimate moisture removal at 13.5 bar gauge with a moderate ambient humidity.
-
−70 °C Desiccant Target
Screen a very low pressure frost point and its atmospheric equivalent.