Humid Shop With a Refrigerated Dryer

Follow 200 SCFM of humid intake air through a 95 °F aftercooler and a 3 °C cold separator.

Inputs

View results ↓
Intake air
°F
%
SCFM
Cooling and drying
psig
°F
°F
h/day

Results

Edit inputs ↑
Moisture removal from intake to outlet PRESS. DP 37.4 °FATM. DP -5.156 °FAFTERCOOLER 22.19 US gal/dayTOTAL DRAIN 32.33 US gal/day AIRFLOW INTAKE 11.79 lb/h AFTERCOOLER 7.715 lb/h DRYER 3.526 lb/h OUTLET 0.5463 lb/h DRAIN DRAIN INLET WATER REMOVED 95.37 % 0% MASS BALANCE 100%
Moisture removal from intake to outlet
Outlet pressure dew point
37.4 °F
Atmospheric dew point
-5.156 °F
Aftercooler liquid drain
22.187 US gal/day
Total collected liquid
32.326 US gal/day
Intake saturation vapor pressure
0.45833 psia
Inlet water vapor
11.787 lb/h
Water removed at aftercooler
7.7148 lb/h
Water removed by dryer
3.5259 lb/h
Outlet water vapor
0.54629 lb/h
Liquid collected at dryer
10.14 US gal/day
Total removal as liquid equivalent
32.326 US gal/day

Formula and assumptions

Compute saturation and intake moisture

Psat = 611.2 exp(aT/(b + T)) · w = 0.621945 Pv/(Pabs − Pv)

T is in °C and vapor pressures are in Pa. Magnus uses a = 17.62 and b = 243.12 over water, and 22.46 and 272.62 over ice below freezing. Enter relative humidity with respect to the phase used. The dry-air flow establishes dry-air mass.

Track water through both stages

Water removed = dry-air mass flow × change in humidity ratio

Limit the entering humidity ratio to saturation at each stage’s pressure and target temperature. A refrigerated dryer’s cold separator can drain liquid. A desiccant target is a pressure dew point, and regeneration typically exhausts the removed water as vapor. Drain estimates use about 1 kg of water per liter and the entered daily hours.

Find pressure and atmospheric dew points

Pv,out = Pline × wout/(0.621945 + wout) · Pv,atm = Pv,out × Pₐₜₘ/Pline

Invert the saturation equation at each vapor pressure. Below freezing the result is a frost point. Values below −65 °C extrapolate the ice fit. ISO 8573-1 class verification requires measured air quality at the point of use.

Flow labels use dry gas at 101.325 kPa, with 60 °F for SCFM and 0 °C for normal metric flow. See all unit conventions.

Worked examples