31-day bill in EUR

A site records 310,000 kWh in 31 days with a 950 kW peak, a 0.125 EUR/kWh rate and 11.70 EUR/kW demand charge.

Inputs

Metered month
Tariff inputs

Load duration and billed demand

50 Hz · MetricEdit inputs
Load duration and billed demand at 50 Hz LOAD FACTOR43.86%BILLED PEAK950kWDEMAND SHARE22.19%MONTH SAVED2.223KEUR/moIllustrative load durationPeak 950 kWStart100% of hoursPeak-shaving bill impactBilled before950 kWBilled after760 kWRatchet floor663 kWLoad factor43.9%100% flat

Detailed results
Billing hours
744 h
Average metered demand
416.67 kW
Monthly load factor
43.86%
Historical ratchet floor
663 kW
Billed demand before
950 kW
Metered peak after
760 kW
Billed demand after
760 kW
Effective metered reduction
190 kW
Baseline energy charge
38,750 EUR
Baseline demand charge
11,115 EUR
Demand share of modeled bill
22.19%
Baseline monthly bill
50,090 EUR
Modeled bill after shaving
47,867 EUR
Baseline blended rate
0.1616 EUR/kWh
Monthly demand savings
2,223 EUR/mo
Annual savings at identical months
26,676 EUR/yr

Worked calculation

Use 744 billing hours for load factor. Add 310,000·0.125 EUR, 950·11.70 EUR and the monthly fixed amount, then divide by 310,000 kWh.

Billing hours
744 h
Baseline monthly bill
50,090 EUR
Baseline blended rate
0.1616 EUR/kWh

Values in this solution use the original example inputs.

Formulas & assumptions

Monthly load factor

Load factor = kWh / (15-minute kW_peak · 24 · billing days)

Enter gross import kWh and the 15-minute measured peak from the same billing period. One interval at peak consumes 0.25 × peak kWh. The load factor is unavailable when the measured peak is zero.

Demand ratchet

kW_billed = max(kW_peak, historical peak · ratchet fraction)

Use the utility’s historical billing window and demand interval. Apply the same ratchet floor before and after shaving. With energy held constant, modeled peak cannot drop below average demand.

Energy, demand and savings

Bill = kWh · energy tariff + billed kW · demand tariff + fixed charge

Divide the baseline bill by kWh for the effective rate. Multiply the decrease in billed kW by the demand tariff to find monthly savings. Annual savings assumes twelve identical months.

A flat energy rate and one non-coincident demand charge, with optional look-back ratchet and fixed fee. Use the actual utility bill and interval data for time-of-use periods, coincident peaks, power-factor charges or seasonal ratchets.