Industrial demand charge & peak shaving calculator

Analyze 15-minute industrial demand, monthly load factor, ratchet floors, blended energy cost and bill savings from lowering the peak.

Inputs

Metered month
Tariff inputs

Load duration and billed demand

60 Hz · US customaryEdit inputs
Load duration and billed demand at 60 Hz LOAD FACTOR39.06%BILLED PEAK640kWDEMAND SHARE41.43%MONTH SAVED2.128KUSD/moIllustrative load durationPeak 640 kWStart100% of hoursPeak-shaving bill impactBilled before640 kWBilled after525 kWRatchet floor525 kWLoad factor39.1%100% flat
  • The historical ratchet sets the billed demand after shaving.

Detailed results
Billing hours
720 h
Average metered demand
250 kW
Monthly load factor
39.06%
Historical ratchet floor
525 kW
Billed demand before
640 kW
Metered peak after
505 kW
Billed demand after
525 kW
Effective metered reduction
135 kW
Baseline energy charge
16,560 USD
Baseline demand charge
11,840 USD
Demand share of modeled bill
41.43%
Baseline monthly bill
28,580 USD
Modeled bill after shaving
26,452.5 USD
Baseline blended rate
0.1588 USD/kWh
Monthly demand savings
2,127.5 USD/mo
Annual savings at identical months
25,530 USD/yr

Formulas & assumptions

Monthly load factor

Load factor = kWh / (15-minute kW_peak · 24 · billing days)

Enter gross import kWh and the 15-minute measured peak from the same billing period. One interval at peak consumes 0.25 × peak kWh. The load factor is unavailable when the measured peak is zero.

Demand ratchet

kW_billed = max(kW_peak, historical peak · ratchet fraction)

Use the utility’s historical billing window and demand interval. Apply the same ratchet floor before and after shaving. With energy held constant, modeled peak cannot drop below average demand.

Energy, demand and savings

Bill = kWh · energy tariff + billed kW · demand tariff + fixed charge

Divide the baseline bill by kWh for the effective rate. Multiply the decrease in billed kW by the demand tariff to find monthly savings. Annual savings assumes twelve identical months.

A flat energy rate and one non-coincident demand charge, with optional look-back ratchet and fixed fee. Use the actual utility bill and interval data for time-of-use periods, coincident peaks, power-factor charges or seasonal ratchets.

Engineering references

Worked examples