Worked calculation
The ratchet floor is 525 kW. A 135 kW shave yields a 505 kW metered peak, so billed demand drops from 640 to 525 kW. Multiply 115 kW by 18.50 USD/kW.
- Monthly load factor
- 39.06%
- Billed demand after
- 525 kW
- Monthly demand savings
- 2,127.5 USD/mo
Values in this solution use the original example inputs.
Formulas & assumptions
A flat energy rate and one non-coincident demand charge, with optional look-back ratchet and fixed fee. Use the actual utility bill and interval data for time-of-use periods, coincident peaks, power-factor charges or seasonal ratchets.