Constant-load billing baseline

A facility runs at 300 kW continuously for 30 days and records 216,000 kWh.

Inputs

Metered month
Tariff inputs

Load duration and billed demand

60 Hz · US customaryEdit inputs
Load duration and billed demand at 60 Hz LOAD FACTOR100%BILLED PEAK300kWDEMAND SHARE13.58%MONTH SAVED0USD/moIllustrative load durationPeak 300 kWStart100% of hoursPeak-shaving bill impactBilled before300 kWBilled after300 kWRatchet floor0 kWLoad factor100%100% flat
  • After-shave demand is floored at average load because monthly kWh is held constant.

Detailed results
Billing hours
720 h
Average metered demand
300 kW
Monthly load factor
100%
Historical ratchet floor
0 kW
Billed demand before
300 kW
Metered peak after
300 kW
Billed demand after
300 kW
Effective metered reduction
0 kW
Baseline energy charge
23,760 USD
Baseline demand charge
3,750 USD
Demand share of modeled bill
13.58%
Baseline monthly bill
27,620 USD
Modeled bill after shaving
27,620 USD
Baseline blended rate
0.1279 USD/kWh
Monthly demand savings
0 USD/mo
Annual savings at identical months
0 USD/yr

Worked calculation

The peak and average are both 300 kW, giving a 100% load factor. With monthly energy fixed there is no demand reduction below that average.

Monthly load factor
100%
Metered peak after
300 kW
Monthly demand savings
0 USD/mo

Values in this solution use the original example inputs.

Formulas & assumptions

Monthly load factor

Load factor = kWh / (15-minute kW_peak · 24 · billing days)

Enter gross import kWh and the 15-minute measured peak from the same billing period. One interval at peak consumes 0.25 × peak kWh. The load factor is unavailable when the measured peak is zero.

Demand ratchet

kW_billed = max(kW_peak, historical peak · ratchet fraction)

Use the utility’s historical billing window and demand interval. Apply the same ratchet floor before and after shaving. With energy held constant, modeled peak cannot drop below average demand.

Energy, demand and savings

Bill = kWh · energy tariff + billed kW · demand tariff + fixed charge

Divide the baseline bill by kWh for the effective rate. Multiply the decrease in billed kW by the demand tariff to find monthly savings. Annual savings assumes twelve identical months.

A flat energy rate and one non-coincident demand charge, with optional look-back ratchet and fixed fee. Use the actual utility bill and interval data for time-of-use periods, coincident peaks, power-factor charges or seasonal ratchets.