Worked calculation
The peak and average are both 300 kW, giving a 100% load factor. With monthly energy fixed there is no demand reduction below that average.
- Monthly load factor
- 100%
- Metered peak after
- 300 kW
- Monthly demand savings
- 0 USD/mo
Values in this solution use the original example inputs.
Formulas & assumptions
A flat energy rate and one non-coincident demand charge, with optional look-back ratchet and fixed fee. Use the actual utility bill and interval data for time-of-use periods, coincident peaks, power-factor charges or seasonal ratchets.