50 Hz natural gas standby set

A plant switching to pipeline gas needs standby power for 280 kW of running load plus a 145 kVA step.

Inputs

Connected load
Site & fuel
A value of 1 uses the illustrative fuel curve. Use model-specific fuel data for final selection.

Load pickup and fuel consumption

50 Hz · MetricEdit inputs
Load pickup and fuel consumption at 50 Hz STANDBY KW387.11kWSTANDBY KVA483.89kVASITE CAPACITY96.48%TANK RUNTIME—Modeled load stepSite limit 466.8 kVARunningPickupIllustrative fuel curveIdle → full load0%100% kWGas lineSite rating96.5% retained100% rated
  • Pipeline natural gas runtime depends on continued gas supply. Tank autonomy applies to diesel.

Detailed results
Required standby nameplate power
387.11 kW
Required standby nameplate capacity
483.89 kVA
Available capacity factor
96.48%
Elevation derating
2.45%
Temperature derating
1.1%
Pre-step running apparent power
321.84 kVA
Modeled pickup apparent power
466.84 kVA
Modeled pickup real power
330.75 kW
Available standby power at site
373.47 kW
Available standby capacity at site
466.84 kVA
Running load on nameplate
72.33%
Fuel rate at running load
99.02 std m³/h
Fuel rate at 25% of nameplate
48.23 std m³/h
Fuel rate at 50% of nameplate
74.54 std m³/h
Fuel rate at 75% of nameplate
101.94 std m³/h
Fuel rate at 100% of nameplate
131.54 std m³/h
Usable diesel volume
Unavailable
Estimated diesel runtime
Unavailable

Worked calculation

First test real and apparent pickup against the derated nameplate. Interpolate the standard-volume gas profile at running/nameplate kW. Tank autonomy is unavailable for pipeline gas.

Required standby nameplate power
387.11 kW
Fuel rate at running load
99.02 std m³/h
Estimated diesel runtime
Unavailable

Values in this solution use the original example inputs.

Formulas & assumptions

Site derating

d = (1 − 0.035 · max(0, ft − 500)/1000) · (1 − 0.01 · max(0, °F − 77)/10)

Each factor applies continuously above its threshold. These are screening slopes, so use the engine and alternator manufacturer’s temperature and altitude ratings for selection.

Steady load and motor pickup

S_pickup = P_run/PF_run + S_step, P_pickup = P_run + S_step · PF_step

Treat running and step kVA as an arithmetic upper estimate. Divide by d. At the entered generator nameplate PF, size for whichever condition requires more kVA.

Fuel and sub-base tank

Runtime = tank volume · usable fraction / fuel rate at running load

Linearly interpolate the generic profile by fraction of standby nameplate kW. Diesel coefficients per rated kW are 0.010, 0.024, 0.039, 0.054 and 0.070 US gal/h at idle, 25%, 50%, 75% and 100%. Natural gas coefficients are 2.8, 4.4, 6.8, 9.3 and 12.0 scf/h at those points.

Screening model for standby service. Confirm site duty ratings, motor-start voltage and frequency excursions, and fuel curves with the equipment manufacturer. Pipeline gas has no sub-base tank runtime.

Engineering references

More worked examples