Worked calculation
Both derating losses are zero at the thresholds. The running apparent load is 96/0.8 = 120 kVA, and the preliminary pickup capacity is 165 kVA.
- Available capacity factor
- 100%
- Required standby nameplate capacity
- 165 kVA
- Fuel rate at running load
- 6.95 gal/h
Values in this solution use the original example inputs.
Formulas & assumptions
Screening model for standby service. Confirm site duty ratings, motor-start voltage and frequency excursions, and fuel curves with the equipment manufacturer. Pipeline gas has no sub-base tank runtime.